AND ANSWERS RATED A+
✔✔Proprietary Supervisory Station Service - ✔✔What type of supervising station fire
alarm system is characterized by the bldg .Which are protected and the supervising
station being under the same ownership?
✔✔FPLP - ✔✔which of the following are acceptable cable for use in an environmental
air return space ?
✔✔monthly - ✔✔Consider a household fire alarm system which communicates to a
supervising station .What type is the testing frequency for the communication path?
✔✔2 devices - ✔✔In corridors where more than _____ visible notification appliances
are in any field of view they ,shall be synchronized.
✔✔6 smk det - ✔✔Consider a room with smooth a flat 10' ceiling which is 60' x 90'
.What is the minimum number of smoke detectors required to cover this space?
✔✔Check for breathing - ✔✔what measures should be taken after determining the
extent of a wounded person injury?
✔✔16 feet - ✔✔Consider the use of visible appliances in sleeping areas.For rooms with
a linear dimension greater than 16 feet, the visible appliance shall be located within
_____feet of the pillow?
✔✔18 months - ✔✔When a device is inaccessible due to excessive height, such as an
atrium, what it the maximum interval for testing?
✔✔30 days - ✔✔supervising station customers shall be notified in writing of any
schedule change in service that results in signals being handled by a different
supervising station. what frame shall this requirement comply within?
, ✔✔300 volts - ✔✔PLFA cables shall be have a voltage rating of not less than ____
volts.
✔✔Solid Joist Construction - ✔✔Ceiling that have solid structural or solid non structural
member projecting down from the ceiling surface for a distance of more the 4 inches
and spaced at intervals of 3 feet or less center to center are identified as which of the
following ?
✔✔95 CD - ✔✔A visible appliance is required in a 50' x 50' square room. A single
appliance will be ceiling mounted at a high of 30'. What candela rating is required?
✔✔CPM - ✔✔which of the following is an acceptable substitution for FPLP cable ?
✔✔Semi annually - ✔✔What is the testing frequency for valve supervisory switches?
✔✔9 conductors - ✔✔what is the maximum number of 14 AWG XHH conductors which
can be installed in 1/2" liquid tight flexible nonmetallic ?
✔✔FPLP - ✔✔Which of the following is an acceptable cable for use in an environmental
air return space?
✔✔Smoke Detector - ✔✔Consider working drawing which have symbol which is a
hexagon with a "S" inside of it. What does this symbol represent?
✔✔Return air system duct detectors shall not be required - ✔✔Consider an application
where all areas serviced by the air return system are provided with total coverage of
smoke detectors. Which of the following is true ?
✔✔10 seconds - ✔✔Fire safety functions and annunciations at the protected premises ,
along with , actuation of notification appliances or emergency voice communication
,shall occur within what time frame after the actuation of an initiating device.
✔✔Signals can be transmitted to other system - ✔✔Consider a video image smoke
detection system .Which of the following is true for video signals generated by cameras
?
✔✔Perform the Heimlich Maneuver - ✔✔What immediate action should be taken to
save the life of a choking victim ?
✔✔60-80 BPM - ✔✔The average of pulse rate of an adult is
✔✔heat exhaustion - ✔✔what heat related conditions exhibits symptoms which include
pale cool and moist skin, with rapid and shallow breathing, headaches , dizziness and
nausea?