ICC Vapor Recovery - VT Questions with Answers (100% Correct Answers)
Type of sealant you should you use on a Phil-Tite Ball Float nipple: —Answer: Pipe dope
Number of open valves on the clean air separator: —Answer: One
You must be CERTIFIED by Healy to re-connect a Healy breakaway, True or False? —Answer:
False
The type of pressure gauge is recommended to test Healy Vac —Answer: SYSA gauge
measuring 0-100 WC
On new construction, after July 1, 2004, Can you install an in-ground Spill Bucket? —Answer:
YES-When Piping is monitored and with VAC
According to Executive Order 201 - Healy P/V Valve should be torqued at —Answer: 20-50 ft-
lbs
For a fire to burn, these (3) three primary elements m After backfilling the vapor return and
vent lines, the maximum pressure drop through the system shall not exceed ________at 60 cubic
feet per hour as determined by TP-201.4, Dynamic Backpressure.
a. 0.75 inches WC
b. 0.5 inches WC
c. 0.32 inches WC
d. 0.55 inches WC —Answer: c. 0.5 inches WC
© 2025 All rights reserved
,CARB's most recent vapor recovery regulations are known as:
a. EVR (enhanced vapor recovery)
b. CVR (California vapor recovery)
c. PVR (protective vapor recovery)
d. ORVR (onboard refueling vapor recovery) —Answer: a. EVR (enhanced vapor recovery)
A valve installed in a motor-vehicle fueling hose designed to separate with little or no product
a. breakaway
b. hose clamp
c. sheer valve
d. flow limiter —Answer: a. breakaway
A Gilbarco Vapor VAC/OPW Vapor Saver system is consdered to have a vapor recovery
equipment defect (VRED) if the vapor escape guard on an OPW 12 VW nozzle is missing or
damaged on at least ____ % of the circumference of the device.
a. 25
b. 50
c. 75
© 2025 All rights reserved
,d. 100 —Answer: c. 75
The two point Phase I vapor recovery system requires that a separate vapor recovery riser pipe
be installed in the tank and be equipped with a:
a. drop tube
b. locking block valve
c. pressure/vacuum vent
d. vapor recovery adaptor —Answer: d. vapor recovery adaptor....
When removing liquid from a sump or spill bucket and the liquid contains fuel, it must be:
a. managed as hazardous waste
b. pumped into a bucket to evaporate
c. scooped or balled onto the concrete pad
d. put it in a sealed container and put into a dump —Answer: a. managed as hazardous waste
One of the approved methods of overfill prevention is to have an overfill device that will
automatically shut off the fill to the tank when the tank is at a maximum of ____ % full.
a. 80
b. 90
© 2025 All rights reserved
, c. 95
d. 99 —Answer: c. 95
What is the appropriate way to clean up a small spill of gasoline?
a. Allow product to evaporate from the area.
b. Wash the spilled product from the area with water.
c. Apply absorbent to the affected area to prevent evaporation.
d. Apply absorbent to the affected area, then remove and dispose of absorbent in accordance
with applicable requirements. —Answer: d. Apply absorbent to the affected area, then remove
and dispose of absorbent in accordance with applicable requirements.
Which of the following is not an overfill prevention device?
a. ball float
b. spill bucket
c. tank overfill alarm
d. drop tube flapper valve —Answer: b. spill bucket
According to PEI RP300, a combustible gas indicator can be used to:
a. determine carbon dioxide levels