A fire department access road is permitted to be what maximum distance from any portion of
the exterior wall of a building - ANS 150 Ft
What is the class of an interior wall and ceiling finish that has a flame spread index of 38 and a
smoke developed index of 150 - ANS Class b
What is the minimum frequency that employees of airport traffic control towers be instructed
on an emergency action plan - ANS Annual
How often do pipes and fittings for a dry system need to be inspected - ANS Annual
A vocational tech school has a woodworking shop used for educational purposes. What is the
occupant load factor for this type of use - ANS 50 net ft
What minimum total combined hose stream allowance is required for a hydraulically calculated
sprinkler system protecting an extra hazard area - ANS 500 gpm
Foam agents are most common to what class of fires? - ANS Class A and B
When operated at maximum speed fully open indicating valves must remain open for what
minimum amount of time before closing - ANS 5 seconds
COPYRIGHT © 2025 BRAINBARTER ALL RIGHTS RESERVED 1
, How much advance notice is required when inspector is investigating a complaint concerning
serious fire and life safety violations - ANS No advance notice is required
What is the maximum occupant load allowed for an existing sprinkler two story assembly
occupancy of type ll [000] construction - ANS 300
When dots an inspector have the authority to order occupants to vacate a building - ANS If
an immediate danger exist
Which of the following is a verbal affirmation or declaration made under oath in a court of law -
ANS Testimony
Which stage of a fire within a compartment does the fuel source produce some heat but has
not yet spread to other substances nearby - ANS Incipient
An automatic sprinkler system is required in an airport terminals concourse when it exceeds
what total floor area - ANS 12,000 ft
Which of the following is describe as the propagation of a flame over a surface - ANS Flame
spread
Which flammable and combustible liquids must be stored in a closed tanks or containers when
not in use and ambient or process temperatures are at or above their flash points - ANS Class
II and III
Manual fire alarm box shall be located within how many inches of exit doorways - ANS 60
inches
How often do monitor nozzles used with private service mains need to be inspector -
ANS Semiannual