Assignment 2 Solutions Winter 2020 1 1. A condominium unit has a single exterior surface of 60 m2 facing the south orientation in Ottawa. The window-to-wall area ratio is 0.5. The R-SI of the wall is 5 m2 ·K/W. The infiltration rate is 0.25 L/s·m2 of the exterior wall surface area. Thickness of the concrete floor slab is 0.2 m. The floor area is 100 m2 . While selecting the window U-SI value, you want to make sure that your building is resilient to a three-day power outage in the winter. Your design objective is that the temperature of the building will not be less than 10°C after a three-day power outage. Assume that the outdoor temperature is constant at -10°C for the three-day analysis period. Neglect solar and internal heat gains. When the power outage starts, assume that the temperature of the unit is 22°C at the onset of the power outage. Treat the unit as a single lumped capacitance. Assume the density, specific heat, and thermal conductivity of the concrete slab as 2300 kg/m3 , 800 J/kg·K, and 1 W/m·K, respectively; and the specific heat and density of air as 1.2 kg/m3 and 1000 J/ kg·K, respectively. Lumped capacitance of concrete slab:

Montrer plus Lire moins
Établissement
Cours

Aperçu du contenu

CIVE 3209 Assignment 2 Solutions Winter 2020


1. A condominium unit has a single exterior surface of 60 m2 facing the south orientation in Ottawa.
The window-to-wall area ratio is 0.5. The R-SI of the wall is 5 m2·K/W. The infiltration rate is 0.25
L/s·m2 of the exterior wall surface area. Thickness of the concrete floor slab is 0.2 m. The floor
area is 100 m2. While selecting the window U-SI value, you want to make sure that your building is
resilient to a three-day power outage in the winter. Your design objective is that the temperature of
the building will not be less than 10°C after a three-day power outage. Assume that the outdoor
temperature is constant at -10°C for the three-day analysis period. Neglect solar and internal heat
gains. When the power outage starts, assume that the temperature of the unit is 22°C at the onset of
the power outage. Treat the unit as a single lumped capacitance. Assume the density, specific heat,
and thermal conductivity of the concrete slab as 2300 kg/m3, 800 J/kg·K, and 1 W/m·K,
respectively; and the specific heat and density of air as 1.2 kg/m3 and 1000 J/ kg·K, respectively.


Lumped capacitance of 𝐶 = 𝑐𝑐𝑜𝑛𝑐 ∙ 𝑣𝑐𝑜𝑛𝑐 ∙ 𝜌𝑐𝑜𝑛𝑐
concrete slab:
= 800 𝐽⁄𝑘𝑔𝐾 ∙ (100𝑚2 × 0.2𝑚) ∙ 2300 𝑘𝑔⁄𝑚3
𝐶 = 36,800,000 𝐽/𝐾


Total system resistance: −𝑡
𝑇(𝑡) = 𝑇𝑜𝑎 + (𝑇𝑡=0 − 𝑇𝑜𝑎 )𝑒 𝑅𝐶 where t @ 3 days = 259,200s
−259200𝑠
10℃ = −10℃ + (22℃ − (−10℃))𝑒 𝑅×36,800,000 𝐽/𝐾
𝑅 = 0.015 𝐾/𝑊


U-SI of window: −1
𝐴𝑤𝑎𝑙𝑙
𝑅=( + 𝐴𝑤𝑖𝑛 𝑈𝑤𝑖𝑛 + 𝑐𝑎𝑖𝑟 ∙ 𝑞𝑖𝑛𝑓 ∙ 𝐴𝑤𝑎𝑙𝑙 ∙ 𝜌𝑎𝑖𝑟 )
𝑅𝑤𝑎𝑙𝑙
30𝑚2 1𝑚3
0.015 𝐾/𝑊 = (5𝑚2 𝐾⁄𝑊 + 30𝑚2 × 𝑈𝑤𝑖𝑛 + 1000 𝐽⁄𝑘𝑔𝐾 ∙ 0.25 𝐿⁄𝑠𝑚2 × (1000𝐿) ∙ 60𝑚2 ∙
−1
1.2 𝑘𝑔⁄𝑚3 )

𝑈𝑤𝑖𝑛 = 1.42 𝑊 ⁄𝑚2 𝐾


Therefore, the window would need to have a maximum U-SI of 1.42 W/m2K to ensure the temperature does not drop
below 10˚C during the three-day power outage.




1

, CIVE 3209 Assignment 2 Solutions Winter 2020


2. You are hired to commission one of the two air handling units in Canal Building. During a site visit
on a cold winter day, you took the measurements indicated in the figure below. For simplicity,
assume that the density of air 1.2 kg/m3 in all your calculations.
(i) In less than 200 words, define what an air handling unit is and explain its four modes of
operation (i.e., heating, economizer, economizer with cooling, cooling).
(ii) Determine the outdoor air fraction. Compare it to the outdoor and return air damper
positions. Interpret your results from this comparison.
(iii) Determine the outdoor airflow rate in L/s.
(iv) Determine the sensible and latent heating rate in kW.
(v) Determine the humidification rate in g/s.
(vi) Assuming that heating and humidifier coils can linearly control the sensible and latent
heating rates, determine the coils’ capacity.
(vii) If we need to provide 10 L/s-person outdoor air for ventilation purposes and if the
building is used by 250 occupants, comment on the outdoor airflow rate calculated in (iii).
(viii) Without changing the supply airflow rate, temperature, and humidity, what would you do
to change the outdoor airflow rate to 2,500 L/s (250 x 10 L/s)? Estimate the reduction in
sensible and latent heating rate in kW and percentage points.




(i) Definitions:
An air handling unit (AHU) is the main component of a forced-air system that conditions the supply air to adequate
temperature and IAQ requirements. This is achieved by bringing in a combination of fresh outdoor and return air into a
mixing plenum via a series of dampers, where this air is filtered, heated/cooled, and humidified. An AHU is supported
by a chiller and boiler to provide cooling or heating via coils in the unit. In the heating mode, AHUs bring in the
minimum outdoor air required to meet IAQ requirements, with the heating coil operating to bring the colder mixed air
up to temperature. In the economizer mode, outdoor air is brought in as required to meet the target supply air
temperature without the use of heating or cooling coils. In the economizer/cooling mode, the unit brings in 100%
outdoor air and cools this air with the cooling coil as needed. In the mechanical cooling mode, outdoor air is once again
brought in at a minimum and conditioned entirely by the cooling coil.




2

École, étude et sujet

Cours

Infos sur le Document

Publié le
22 mars 2023
Nombre de pages
15
Écrit en
2022/2023
Type
Examen
Contient
Questions et réponses

Sujets

€8,56
Accéder à l'intégralité du document:

Garantie de satisfaction à 100%
Disponible immédiatement après paiement
En ligne et en PDF
Tu n'es attaché à rien

Faites connaissance avec le vendeur

Seller avatar
Les scores de réputation sont basés sur le nombre de documents qu'un vendeur a vendus contre paiement ainsi que sur les avis qu'il a reçu pour ces documents. Il y a trois niveaux: Bronze, Argent et Or. Plus la réputation est bonne, plus vous pouvez faire confiance sur la qualité du travail des vendeurs.
ExamsConnoisseur Self
S'abonner Vous devez être connecté afin de suivre les étudiants ou les cours
Vendu
579
Membre depuis
3 année
Nombre de followers
344
Documents
1497
Dernière vente
6 jours de cela

4,2

68 revues

5
40
4
11
3
13
2
1
1
3

Documents populaires

Récemment consulté par vous

Pourquoi les étudiants choisissent Stuvia

Créé par d'autres étudiants, vérifié par les avis

Une qualité sur laquelle compter : rédigé par des étudiants qui ont réussi et évalué par d'autres qui ont utilisé ce document.

Le document ne convient pas ? Choisis un autre document

Aucun souci ! Tu peux sélectionner directement un autre document qui correspond mieux à ce que tu cherches.

Paye comme tu veux, apprends aussitôt

Aucun abonnement, aucun engagement. Paye selon tes habitudes par carte de crédit et télécharge ton document PDF instantanément.

Student with book image

“Acheté, téléchargé et réussi. C'est aussi simple que ça.”

Alisha Student

Foire aux questions