Answers Verified 100% Correct
Which of the following can be used to determine battery capacity?
Hydrometer
Float test
Specific gravity calculation
Load test - ANSWER -Load test
A storage battery must supply AT LEAST .
331⁄3% of the system voltage for the total load of circuits supplying legally
required standby power
671⁄3% of the system voltage for the total load of circuits supplying legally
required standby power
871⁄2% of the system voltage for the total load of circuits supplying legally
required standby power
100% of the system voltage for the total load of circuits supplying legally required
standby power - ANSWER -871⁄2% of the system voltage for the total load of
circuits supplying legally required standby power
Each patient bed location in a health care facility MUST be supplied by .
one or more branch circuits from the emergency system only
one branch circuit from the normal electrical system only
two branch circuits from the emergency system only
one or more branch circuits from the normal electrical system and one or more
from the emergency system - ANSWER -one or more branch circuits from the
normal electrical system and one or more from the emergency system
NEC Article 518 contains .
requirements for places of assembly
information on transferswitches
requirements for health care facilities