NEC Final Exam with correct answers ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
Load calculations must be performed in order to determine the _____________ - correct
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔size of the service and feeders ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
A feeder is defined as all the circuit conductors between the __________ containing fuses or
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
breakers that feed branch circuits - correct answer✔✔service disconnecting means and the
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
panelboard
_______________ are included in the calculated floor area of dwelling units - correct ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔Open porches ||\\||\\
A scale ruler is used in - correct answer✔✔determining the location of outlets
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The ___________ is NOT an important piece of information to gather before performing load
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
calculations - correct answer✔✔location of circuit breakers
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The __________, including the strip heat and blower motor, is necessary information for
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
calculating loads - correct answer✔✔total volt-ampere load ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The lighting load for residential dwelling units is _____________ volt-amperes (VA) per
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
square foot - correct answer✔✔3 ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The ____________ for each floor of a one-family dwelling shall be computed using the
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
outside dimensions - correct answer✔✔floor area ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
,_______________ must be included when calculating a dwelling unit service - correct ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔Small-appliance branch circuits ||\\||\\ ||\\||\\
A dwelling unit must have at least ______________ small-appliance branch circuit(s). -
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
correct answer✔✔2 ||\\||\\ ||\\||\\
Each laundry branch circuit is calculated at _______________ - correct answer✔✔no less
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
than 1500 volt-amperes ||\\||\\ ||\\||\\
Individual household cooking appliances rated more than ___________ watts (volt-amperes)
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
can be derated by using Table 220.55 demand factors ( and all of the appliance notes). -
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
correct answer✔✔1750 ||\\||\\ ||\\||\\
No derating is allowed when there are only one, two, or three ____________ appliances. -
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
correct answer✔✔fastened-in place ||\\||\\ ||\\||\\ ||\\||\\
The term _______________ designates utilization equipment commonly built in standardized
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
types and sizes and installed as a unit the perform specific function(s). - correct
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔appliance
Multiplying voltage by amperage produces ____________. - correct answer✔✔volt-amperes ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
(VA)
A clothes dryer neutral load on a feeder can be calculated at ___________%. - correct
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔70
Horsepower ratings must be converted to ______________ before they can be added to the ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
load calculation form. - correct answer✔✔volt-amperes (VA)
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
, The smaller of two (or more) ____________ loads can be omitted, as long as they are never
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
energized simultaneously. - correct answer✔✔noncoincedent ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
For the purpose of the standard method load calculation for a one-family dwelling, the terms
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
neutral and ____________ are synonymous. - correct answer✔✔grounded
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
A demand factor of ___________% can be applied to the nameplate rating load of four or
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
more fastened-in-place appliances. - correct answer✔✔75
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
In outdoor applications, ___________ grounding electrode conductors must not be installed
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
within 18in (450 mm) of the earth. - correct answer✔✔aluminum
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
______________ are not included in calculating receptacle loads for appliances. - correct ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔Air-conditioning systems ||\\||\\
The exact nameplate rating of the clothes dryer, even if less than ___________ volt-amperes
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
should be used in load calculations. - correct answer✔✔5000||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
For a service rated 100 through 400 A, the service conductors supplying the entire load
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
associated with a one-family dwelling shall be permitted to have an ampacity not less ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
____________ % of the service rating. - correct answer✔✔83 ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The minimum size grounding electrode conductor is ____________ AWG copper ( or 4 AWG
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
aluminum). - correct answer✔✔6 ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
Service-entrance and overhead service conductors shall be arranged so that ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
_________________. - correct answer✔✔water shall not enter the service raceway or ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
equipment
Load calculations must be performed in order to determine the _____________ - correct
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔size of the service and feeders ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
A feeder is defined as all the circuit conductors between the __________ containing fuses or
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
breakers that feed branch circuits - correct answer✔✔service disconnecting means and the
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
panelboard
_______________ are included in the calculated floor area of dwelling units - correct ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔Open porches ||\\||\\
A scale ruler is used in - correct answer✔✔determining the location of outlets
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The ___________ is NOT an important piece of information to gather before performing load
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
calculations - correct answer✔✔location of circuit breakers
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The __________, including the strip heat and blower motor, is necessary information for
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
calculating loads - correct answer✔✔total volt-ampere load ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The lighting load for residential dwelling units is _____________ volt-amperes (VA) per
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
square foot - correct answer✔✔3 ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The ____________ for each floor of a one-family dwelling shall be computed using the
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
outside dimensions - correct answer✔✔floor area ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
,_______________ must be included when calculating a dwelling unit service - correct ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔Small-appliance branch circuits ||\\||\\ ||\\||\\
A dwelling unit must have at least ______________ small-appliance branch circuit(s). -
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
correct answer✔✔2 ||\\||\\ ||\\||\\
Each laundry branch circuit is calculated at _______________ - correct answer✔✔no less
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
than 1500 volt-amperes ||\\||\\ ||\\||\\
Individual household cooking appliances rated more than ___________ watts (volt-amperes)
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
can be derated by using Table 220.55 demand factors ( and all of the appliance notes). -
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
correct answer✔✔1750 ||\\||\\ ||\\||\\
No derating is allowed when there are only one, two, or three ____________ appliances. -
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
correct answer✔✔fastened-in place ||\\||\\ ||\\||\\ ||\\||\\
The term _______________ designates utilization equipment commonly built in standardized
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
types and sizes and installed as a unit the perform specific function(s). - correct
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔appliance
Multiplying voltage by amperage produces ____________. - correct answer✔✔volt-amperes ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
(VA)
A clothes dryer neutral load on a feeder can be calculated at ___________%. - correct
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔70
Horsepower ratings must be converted to ______________ before they can be added to the ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
load calculation form. - correct answer✔✔volt-amperes (VA)
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
, The smaller of two (or more) ____________ loads can be omitted, as long as they are never
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
energized simultaneously. - correct answer✔✔noncoincedent ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
For the purpose of the standard method load calculation for a one-family dwelling, the terms
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
neutral and ____________ are synonymous. - correct answer✔✔grounded
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
A demand factor of ___________% can be applied to the nameplate rating load of four or
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
more fastened-in-place appliances. - correct answer✔✔75
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
In outdoor applications, ___________ grounding electrode conductors must not be installed
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
within 18in (450 mm) of the earth. - correct answer✔✔aluminum
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
______________ are not included in calculating receptacle loads for appliances. - correct ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
answer✔✔Air-conditioning systems ||\\||\\
The exact nameplate rating of the clothes dryer, even if less than ___________ volt-amperes
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
should be used in load calculations. - correct answer✔✔5000||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
For a service rated 100 through 400 A, the service conductors supplying the entire load
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
associated with a one-family dwelling shall be permitted to have an ampacity not less ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
____________ % of the service rating. - correct answer✔✔83 ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
The minimum size grounding electrode conductor is ____________ AWG copper ( or 4 AWG
||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
aluminum). - correct answer✔✔6 ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
Service-entrance and overhead service conductors shall be arranged so that ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
_________________. - correct answer✔✔water shall not enter the service raceway or ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\ ||\\||\\
equipment