Ups battery systems are required to be filed and approved by - CORRECT ANSWER -
The nyc department of buildings
COF holders are only allowed to make - CORRECT ANSWER -Visual inspections
UPS systems installed on or after July 1 2008 shall - CORRECT ANSWER -
Comply with the fire code edition in effect at the time they were installed.
UPS battery systems that were installed before July 1 200(pre existing systems) shall -
CORRECT ANSWER -
Not be required to comply with the design, installation, and ventilation requirements of the
2007 or 2014 fire code.
Any better system in place, regardless of installation date, must be under the -
CORRECT ANSWER -General supervision.
QUICK visual inspections shall be performed - CORRECT ANSWER -Once a day
The environment for cells should be - CORRECT ANSWER -Clean, cool, and dry.
A UPS room should have what kind of alarm system? - CORRECT ANSWER -
Hydrogen detector.
Hazards
High voltage electricity
, -fire
-explosion
-electrical and high Temperature burns - CORRECT ANSWER -
If any of the above incidents occur, contact 911 immediately.
Possible causes of an explosion would be: - CORRECT ANSWER -Electrolyte Overcharge
Safety valve or vents dial due to excess dirt and debris.
Hazard
Gas release - CORRECT ANSWER -Explosion
Personal injury
Hazard
Hydrogen gas - CORRECT ANSWER -Odorless gas
Highly flammable
(Lower explosion limits 4.0, Upper explosion limits 75.0).
Citywide standard key - CORRECT ANSWER -Also known as a "2642" key
Capacity test - CORRECT ANSWER -
A controlled constant current or constant power discharge of a battery to a specified termin
al voltage.