Operating devices shall operate at. ANSWER -32F to 120F
Manual actuators shall not have a force more than. ANSWER -40lbs
Manual actuators shall not have a movement of more than. ANSWER -14 inches
Instructions with pictographs and lettering shall be atleast. ANSWER -1/4 inches
Pipe and fittings shall be made of. ANSWER -Non combustible materials
galvanized pipe and fittings. ANSWER -Shall not be used
During assembly examine pipe. ANSWER -Internally to detect and remove contaminants
, Readily acces means for manual actuators. ANSWER -Shall be located in a path of egress
Manual actuators shall be installed. ANSWER -No more than 48in and no less than 42in
Fusible links shall be located. ANSWER -At above each cooking appliance
Fusible links shall be. ANSWER -12 in in front of said item
A test shall be used on pipe using. ANSWER -Nitrogen or dry air not exceeding normal
operating pressure
Piping shall not. ANSWER -Be hydrostatic tested
Owners inspection. ANSWER -Monthly
Owners inspection records shall be retained. ANSWER -Semi-annualy
Wet chemical fire extinguisher service at. ANSWER -Every 6 months
Wet chemical fire extinguishing system service at. ANSWER -6 months
wet chemical fire extinguishing system with fire damage,corrosion,welds etc. ANSWER -
Shall be hydrostatic tested
Maintenance reports shall be kept. ANSWER -For a year
Fixed temperature sensing elements otger than fusible metal alloys shall be replaced.
ANSWER -Every 12 months
Fixed temperature sensing elements of fusible metal alloys shall be replaced. ANSWER -
Semi-annualy
Compliance – Texas Fire Department –
Practice Test Questions and Verified
Answers (Latest Update, Graded A)
QUESTIONS AND ANSWERS
Operating devices shall operate at. ANSWER -32F to 120F
Manual actuators shall not have a force more than. ANSWER -40lbs
Manual actuators shall not have a movement of more than. ANSWER -14 inches
Instructions with pictographs and lettering shall be atleast. ANSWER -1/4 inches
Pipe and fittings shall be made of. ANSWER -Non combustible materials
galvanized pipe and fittings. ANSWER -Shall not be used
During assembly examine pipe. ANSWER -Internally to detect and remove contaminants
, Readily acces means for manual actuators. ANSWER -Shall be located in a path of egress
Manual actuators shall be installed. ANSWER -No more than 48in and no less than 42in
Fusible links shall be located. ANSWER -At above each cooking appliance
Fusible links shall be. ANSWER -12 in in front of said item
A test shall be used on pipe using. ANSWER -Nitrogen or dry air not exceeding normal
operating pressure
Piping shall not. ANSWER -Be hydrostatic tested
Owners inspection. ANSWER -Monthly
Owners inspection records shall be retained. ANSWER -Semi-annualy
Wet chemical fire extinguisher service at. ANSWER -Every 6 months
Wet chemical fire extinguishing system service at. ANSWER -6 months
wet chemical fire extinguishing system with fire damage,corrosion,welds etc. ANSWER -
Shall be hydrostatic tested
Maintenance reports shall be kept. ANSWER -For a year
Fixed temperature sensing elements otger than fusible metal alloys shall be replaced.
ANSWER -Every 12 months
Fixed temperature sensing elements of fusible metal alloys shall be replaced. ANSWER -
Semi-annualy