Corrosion Specialist - ✔✔- ACTUAL ANSWER- designs and certifies cathodic
protection system
Secondary containment shall be constructed to contain at least the following
volumes: - ✔✔- ACTUAL ANSWER- A. 100% of usable capacity of primary
where there is only one primary is within the secondary
B. 150% of the largest container if there are multiple primary containers in a
single secondary
Cathodic protection tester will test cathodic protection system within __ months of
installation and every __ years thereafter - ✔✔- ACTUAL ANSWER- 6 months
3 years
Spill container shall meet the following requirements: - ✔✔- ACTUAL ANSWER-
A. If made of metal, exterior wall shall be protected from galvanic corrosion
B. Shall have minimum capacity of 5 gallons (19 L)
C. Shall have drain valve which allows drainage of the collected spill into the
primary container or provide means to keep spill cont empty
Overfill prevention shall alert transfer operator when tank is __% full - ✔✔-
ACTUAL ANSWER- 90%
Flapper Valves shall provide positive shut off when tank is filled to no more than
__% capacity - ✔✔- ACTUAL ANSWER- 95%
Primary pressurized piping shall be tested for tightness hydrostatically at __% of
design operating pressure - ✔✔- ACTUAL ANSWER- 150%
Date that all UST systems must have Line Leak Detector installed - ✔✔-
ACTUAL ANSWER- November 9,2004
Secondary containment testing shall be done upon ____, __months, and every
___ months or ____ years thereafter - ✔✔- ACTUAL ANSWER- Installation
6 months