MICHIGAN JOURNEYMAN TEST WITH
QUESTIONS AND ANSWERS 100%
VERIFIED
There are six conductors in a race way connected to 75° C rated circuit
breaker. Each wire has a 70 amp load using THHM conductors. The
minimum size conductors used our #_________AWG - correct answer_
4
Thermal insulation shall not be installed within _________inches of
recessed lighting fixtures - correct answer_ 3
A 1 inch conduit contains three wire circuits or a phase system. All
conductors are number 10 TW. Each circuit consist of two phase
conductors and one grounding conductor and one equipment
grounding conductor. The maximum and pasty of each phase conductor
is______. - correct answer_ 24 amps
The volt Ampere rating of a device that consumes 14.5 A on a 240 V
circuit is_____. - correct answer_ 3480watts
, 2|Page
A 208 V, three phase heater draws 3598 W . How many campers does
the heater draw - correct answer_ 10
The underwater light fixture shall be installed at least ________inches
below the water level - correct answer_ 18
A general purpose receptacle shall not be installed on the_________ -
correct answer_ Offense directly south of the pool
A junction box for a 124 wet niche fixture shall be at
least_______Inches above the ground - correct answer_ 4
A GFCI protected_______ receptacle for the pump motor May be
installed on the south side of the dwelling unit dedicated grounding
type - correct answer_ Dedicated receptacle
A metal fence installed within________Feet of a pool Shall be bonded -
correct answer_ 5