S-12 CITYWIDE SPRINKLER SYSTEMS, S12
sprinkler test Questions and Answers
(100% Correct Answers) Already Graded
A+
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND
TO DETERMINE QUALIFICATIONS.—Ans: OWNER
© 2025 Assignment Expert
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS.—Ans: 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO
COMPLY WITH REQUIREMENTS.—Ans: IMPAIRMENT COORDINATOR
Guru01 - Stuvia
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN
________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE.—Ans: 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.—Ans: 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS.—Ans: 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER
SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND
THE FIRE DEPT.—Ans: OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.—Ans:
30
WHAT DOES "OOS" STAND FOR?—Ans: OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE
DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE
COMMAND CENTER—Ans: TAGS
, 2
For Expert help and assignment solutions, +254707240657
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL
VALVE AND ANY SECTIONAL VALVES.—Ans: MASTER FIRE
SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC
AND FLOW PRESSURES BEFORE AND AFTER.—Ans: DRAIN TEST
RESULTS
GREEN TAGS INDICATE THAT __________.—Ans: NO IMPAIRMENT
WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.—Ans: MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
© 2025 Assignment Expert
____________ TAG PLACED ON THE MAIN CONTROL VALVE.—Ans:
RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
Guru01 - Stuvia
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE.—Ans: WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF
SERVICE.—Ans: BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS.—Ans: INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL
ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE
CONDUCTED.—Ans: IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL
NOT GREATHER THAN ________ PERCENT SHALL BE USED TO
PROTECT FROM FREEZING.—Ans: 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE
POSTED NEAR THE ____________.—Ans: MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE
OF THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3
YEARS.—Ans: RECORDS
, 3
For Expert help and assignment solutions, +254707240657
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE
COF AND COURT PROCEEDINGS.—Ans: REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF
THEY HOLD THE FOLLOWING CERTS:—Ans: REFRIGERATION
OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND
NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE
STANDPIPE AND SPRINKLER SYSTEMS.—Ans: MASTER FIRE
SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.—Ans:
© 2025 Assignment Expert
30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR
CONTROLLED WHEN SPRINKLERS ARE INSTALLED.—Ans: 96
Guru01 - Stuvia
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING.—Ans: 40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED.—
Ans: COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM
CANNOT BE HEATED TO PREVENT FREEZING.—Ans: DRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO
OPEN.—Ans: AIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS)
THE ALARM IS TRANSMITTED DIRECTLY TO THE _________.—Ans: FIRE
DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN.—Ans: CLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE
NORMAL TRIP LEVEL.—Ans: 15-20
AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME
TO ALLOW WATER INTO THE SYSTEM.—Ans: REDUCE
BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A
DROP OF _______ PSI IS DETECTED IN THE SYSTEM.—Ans: 2
For Expert help and assignment solutions, +254707240657
S-12 CITYWIDE SPRINKLER SYSTEMS, S12
sprinkler test Questions and Answers
(100% Correct Answers) Already Graded
A+
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND
TO DETERMINE QUALIFICATIONS.—Ans: OWNER
© 2025 Assignment Expert
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON
PREMISES FOR A MIN. OF __________ YEARS.—Ans: 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO
COMPLY WITH REQUIREMENTS.—Ans: IMPAIRMENT COORDINATOR
Guru01 - Stuvia
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN
________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM
SERVICE.—Ans: 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE
CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.—Ans: 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS
RETURNED TO SERVICE WITHIN ______ HOURS.—Ans: 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER
SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND
THE FIRE DEPT.—Ans: OWNER OF THE BUILDING
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN
_________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.—Ans:
30
WHAT DOES "OOS" STAND FOR?—Ans: OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE
DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE
COMMAND CENTER—Ans: TAGS
, 2
For Expert help and assignment solutions, +254707240657
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL
VALVE AND ANY SECTIONAL VALVES.—Ans: MASTER FIRE
SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC
AND FLOW PRESSURES BEFORE AND AFTER.—Ans: DRAIN TEST
RESULTS
GREEN TAGS INDICATE THAT __________.—Ans: NO IMPAIRMENT
WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________.—Ans: MAIN
CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A
© 2025 Assignment Expert
____________ TAG PLACED ON THE MAIN CONTROL VALVE.—Ans:
RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON
Guru01 - Stuvia
CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF
SERVICE.—Ans: WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON
CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF
SERVICE.—Ans: BLUE
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________
CARRIER, CENTRAL STATION AND OCCUPANTS.—Ans: INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL
ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE
CONDUCTED.—Ans: IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL
NOT GREATHER THAN ________ PERCENT SHALL BE USED TO
PROTECT FROM FREEZING.—Ans: 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE
POSTED NEAR THE ____________.—Ans: MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE
OF THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3
YEARS.—Ans: RECORDS
, 3
For Expert help and assignment solutions, +254707240657
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE
COF AND COURT PROCEEDINGS.—Ans: REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF
THEY HOLD THE FOLLOWING CERTS:—Ans: REFRIGERATION
OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND
NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE
STANDPIPE AND SPRINKLER SYSTEMS.—Ans: MASTER FIRE
SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL
OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.—Ans:
© 2025 Assignment Expert
30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR
CONTROLLED WHEN SPRINKLERS ARE INSTALLED.—Ans: 96
Guru01 - Stuvia
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO
PREVENT THE SYSTEM FROM FREEZING.—Ans: 40 FAHRENHEIT
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED.—
Ans: COLD WEATHER
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM
CANNOT BE HEATED TO PREVENT FREEZING.—Ans: DRY PIPE
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO
OPEN.—Ans: AIR PRESSURE
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS)
THE ALARM IS TRANSMITTED DIRECTLY TO THE _________.—Ans: FIRE
DEPARTMENT
DRY PIPE VALVES ARE OF A ______ DESIGN.—Ans: CLAPPER
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE
NORMAL TRIP LEVEL.—Ans: 15-20
AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME
TO ALLOW WATER INTO THE SYSTEM.—Ans: REDUCE
BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A
DROP OF _______ PSI IS DETECTED IN THE SYSTEM.—Ans: 2