A system is supplied from the factory with charge of 5 pounds 10 ounces for a 15 foot line set.
The line set is 25 feet long. The manufacturer's instruction sheet specifies 0.6 ounces of
refrigeration to be added for each added foot of refrigerant line set length. What is the total
refrigerant charge for the system?
A. 6 ounces
B. 5 pounds
C. 5 pounds 10 ounces
D. 6 pounds - CORRECT ANSWER D. 6 pounds
15ft - 25ft = 10ft x .6 = 6 ounces
5 pounds + 10 ounces + 6 ounces
5 pounds + 16 ounces = 6 pounds
The purpose of using flux when soldering is to:
A. anneal the surface.
B. give better heat flow.
C. reduce oxidation.
D. pre-seal the oxidation. - CORRECT ANSWER C. reduce oxidation.
Outdoor condensing units that are installed in areas where flooding is possible must:
A. be mounted above flood level.
,B. utilize NEMA 1 enclosures.
C. be mounted under an overhanging eave.
D. use water resistant components. - CORRECT ANSWER A. be mounted above flood level.
The component used to reduce sound transmission and prevent water leaks on a rooftop air
conditioner packaged unit installation is the:
A. curb gasket.
B. silicone caulk.
C. roof flashing.
D. roofing tar. - CORRECT ANSWER A. curb gasket.
Return air leakage in a hot attic will:
A. Increase capacity
B. Decrease capacity
C. Increase airflow
D. Decrease airflow - CORRECT ANSWER B. Decrease capacity
An air conditioner refrigerant circuit should be evacuated to a minimum of:
A. 0 microns.
B. 200 microns.
C. 500 microns.
D. 1200 microns. - CORRECT ANSWER C. 500 microns.
, Which of the following substances could create an extremely dangerous condition if used to
check refrigeration system for leaks?
A. R-22
B. Nitrogen
C. Oxygen
D. Carbon Dioxide - CORRECT ANSWER D. Carbon Dioxide
The subcooling method for checking charge is generally used on air conditioners with what type
of metering?
A. Only externally equalized thermostatic expansion valves
B. Any thermostatic expansion valve
C. Piston type
D. Any fixed metering device - CORRECT ANSWER B. Any thermostatic expansion valve
Supply ducts running through unconditioned space should be insulated and have:
A. equal friction.
B. excessive air velocity.
C. a vapor barrier.
D. a transition backing. - CORRECT ANSWER C. a vapor barrier.
An important consideration when installing a motorized economizer is to check to be certain
that:
A. the vanes are set for a maximum 10% outdoor air.