When is the interior of the dry pipe alarm
valve cleaned?
NO! CH13.4.4.2.3
Can grease or other sealing materials be
applied to the seating surfaces of dry pipe
valves?
Quarterly CH 13.4.4.2.4
What is the testing frequency of quick
opening devices on dry pipe alarm valves
5 Years CH 13..4.3.3.2.1
What is the interior cleaning interval on dry
pipe alarm valves that can be reset without
removing the faceplate
A sectional drain is located beyond the floor control valve on a multi story building
What is and where can a sectional drain be
located? A3.3.10.2
Yes- each deluge valve is intended to be manually operated A.3.5.2
Is a deluge valve capable of manual
operation?
Downstream of the fire pump's discharge A.3.5.5.1
Where can a master pressure reducing
valve be found?
`The lines overlaid on a map ot the US & Canada that show the lowest one day
mean temperature in the "areas between the marked lines" as identified on Figure
What are Isothermal Lines? A.5.3.4
In locations where chemicals, moisture or other corrosive vapors exist A.5.4.1.6
Where should corrosion resistant or
specially coated fire sprinkler be installed?
10-15 years A.6.3.4
What is normal life expectancy of a PSI
gauge?
What is the minimum flow for a fire pump? Churn Pressure A 8.3.3.1
During periods of unusual water supply conditions such as floods or droughts
Under what conditions should a fire pump
visual inspection be performed daily? A.8.3.3.7
Per the manufacturers recommendations A.8.5.1
What is the recommended temperature of
the fire pump room, pump house or area
where a diesel driven fuel pump is located?
Qualified personnel. CH 4.1.1.2
Who shall perform the inspection, testing
and maintenance of water based fire
protection systems?
The property owner or designated representative CH 4.1.3
Who provides the accessibility of the
components to the water based fire
protection systems for inspection
When a system is returned to service who The AHJ, the fire department and the alarm-receiving facility CH 4.1.4.2
shall be notified?
Are inspection records allowed to be stored Yes. And accessed electronically as well. CH 4.3.1.1
electronically?
what is the frequency of tests? As defined in NFPA-25 CH 4.6.2
1. Procedure or activity performed (inspectiontest-maintenance)
2. Name of the performing arganization
3.The required frequency of the activity
Name 5 items that should be on all 4. THe results and date of the activity performed
inspection records 5.Name & contact information of the qualified contractor
CH 4.3.2