A check valve in an approved backflow assembly must be tight when - Answers The assembly is
subject to any backflow
a leaking check valve may be caused by? - Answers Dirty or damaged check disc, damaged
check seat, broken or damaged spring, guide members hanging up (all of the above)
Test cock number one of an approved double check valve assembly is located - Answers
Upstream on shutoff valve number one
On an approved pressure vacuum breaker assembly, the shut off valves - Answers Are located
at the inlet and outlet of all assemblies
The bypass line of a backflow must contain an approved assembly of equal - Answers
Temperature rating
The bypass line of a backflow must contain an approved assembly of equal - Answers
Protection
An atmospheric pressure vacuum breaker shall not be subjected to water pressure for more
than _______ hours - Answers 12
It is possible for a perfect vacuum at sea level to raise water in a pipe approximately ____ feet? -
Answers 34 feet
What is the most desirable place install a Backflow? - Answers In an accessible location above
ground
Which of the following conditions could result in water contamination through cross connection?
- Answers Turning off service to a multi story building and allowing water supply to drain
The degree of hazard is - Answers BASED UPON THE QUALITY OF A NON POTABLE WATER
SOURCE
The minimum type of containment protection for a non-health hazard, non chemical sprinkler is
- Answers Double check
Type of protection required for a closed loop heating system containing chemicals - Answers
RPZ
Water continuously leaking from test cock #2 during a test procedure of a pressure vacuum
breaker assembly is probably caused by a leaking - Answers INLET SHUT-OFF VALVE #1
The required backflow for a fire sprinkler system containing chemicals is - Answers RPZ
, Required protection of a backflow for a closed loop system containing glycol is - Answers RPZ
Primary consideration in determining what type of backflow to install is - Answers Degree of
hazard
What is the probable cause of a relief valve failing to open during a field test of a RPZ? -
Answers Malfunction of the relief valve mechanism
The required backflow protection for a chemically charged solar heating system with an
expansion tank is? - Answers RPZ
Type of protection associated with an air gap separation is - Answers Backsiphonage & back
pressure ( all of the above)
The application of a pressure vacuum breaker assembly is for - Answers Backsiphonage and
isolation
How many pounds of pressure per square inch are exerted at the base of a column of water that
is two feet tall? - Answers 0.86
A pressure of 75 psi would be equivalent to ____ head of pressure? - Answers 173.2 feet
A gauge installed at the bottom of an open tank, containing water 10 feet deep, would indicate
what pressure reading? - Answers 4.3 psi
What equipment is used to test a pressure vacuum breaker - Answers Differential pressure
gauge
Test cock number ____ may be opened to establish flow through a backflow? - Answers Four
USC, AWWA and manufacturers recommend that backflow prevention assemblies be inspected,
and that their proper operation is verified by a certified tester at least? - Answers Once every
year
A differential pressure gauge is used in the testing of - Answers Double checks and RPZs
What info is required to be properly identify the Backflow assembly to be tested - Answers Type,
manufacturer, location, size, model, serial number (all of the above)
The original signed and tested date test report must be - Answers Submitted to the water
purveyor
The critical final step in testing a backflow prevention assembly is? - Answers Returning the
assembly to normal operating condition
The differential pressure relief valve on a RPZ must open before the differential pressure across
the inlet drops below - Answers 2.0