Neta 3 exam| latest|COMPLETE
FREQUENTLY MOST TESTED QUESTIONS
WITH VERIFIED ANSWERS/ALREADY
GREADED A+ |GET IT 100% ACCURATE!!
Liquid-filled transformer bushing hot-collar acceptance test values that
exceed____ watts should be investigated per NETA ATS - (ANSWER)0
Minimum acceptable megohm value for metal-oxide surge arrester rated 15kv
with Mcov rating 12.7kv - (ANSWER)5000
ASTM D877 dielectric breakdown test, the electrode gap seperation is fixed at -
(ANSWER)2.5mm
Maximum allowed combined frequency variation from nameplate for AC
induction motors? - (ANSWER)10%
NETA-MTS recommended test voltage for a 15 minute withstand test on a single-
phase, 15kV line sectionalizer with a rated impulse withstand voltage of 95 kV -
(ANSWER)39 VDC
Medium voltage switchgear electrical testing and maintenance Every ____
months for high reliability requirement in good condition - (ANSWER)18