NFPA 72 Practice Questions with Actual
Solutions
10 SECONDS
PROTECTED PREMISES SECONDARY POWER SUPPLY PROVIDED WITHIN
60 SECONDS
SUPERVISING STATION FACILITY/EQUIPMENT SECONDARY POWER SUPPLY
PROVIDED WITHIN
QUIESCENT
SYSTEM OPERATING IN NONALARM CONDITION
24 HOURS
SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE
SYSTEM UNDER QUIESCENT LOAD FOR
5 MINUTES
SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE
FIRE ALARM UNDER ALARM LOAD FOR
15 MINUTES
SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE
VOICE EVAC AND MASS NOTIFICATION SYSTEM UNDER ALARM LOAD FOR
TYPE 10, CLASS 24, LEVEL 1
, PROTECTED PREMISES AND EMERGENCY COMMUNICATION SYSTEM
GENERATOR
TYPE 60, CLASS 24, LEVEL 2
SUPERVISING STATION SYSTEM GENERATOR
TYPE M, CLASS 24, LEVEL 2
SUPERVISING STATION SYSTEM MANUAL START GENERATOR
10
ALARM SIGNAL ACTUATION WITHIN (SECONDS)
90
SUPERVISORY SIGNAL ACTUATION WITHIN (SECONDS)
200
TROUBLE SIGNAL ACTUATION WITHIN (SECONDS)
NEXT TEST PLUS 1 YEAR
TESTING RECORDS KEPT UNTIL
5 YEARS PLUS 1 YEAR
RESTORABLE, FIXED-TEMPERATURE, SPOT-TYPE HEAT DETECTORS: TESTING
RECORDS KEPT UNTIL
12 MONTHS
SUPERVISING STATION: TESTING RECORDS KEPT UNTIL
Solutions
10 SECONDS
PROTECTED PREMISES SECONDARY POWER SUPPLY PROVIDED WITHIN
60 SECONDS
SUPERVISING STATION FACILITY/EQUIPMENT SECONDARY POWER SUPPLY
PROVIDED WITHIN
QUIESCENT
SYSTEM OPERATING IN NONALARM CONDITION
24 HOURS
SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE
SYSTEM UNDER QUIESCENT LOAD FOR
5 MINUTES
SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE
FIRE ALARM UNDER ALARM LOAD FOR
15 MINUTES
SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE
VOICE EVAC AND MASS NOTIFICATION SYSTEM UNDER ALARM LOAD FOR
TYPE 10, CLASS 24, LEVEL 1
, PROTECTED PREMISES AND EMERGENCY COMMUNICATION SYSTEM
GENERATOR
TYPE 60, CLASS 24, LEVEL 2
SUPERVISING STATION SYSTEM GENERATOR
TYPE M, CLASS 24, LEVEL 2
SUPERVISING STATION SYSTEM MANUAL START GENERATOR
10
ALARM SIGNAL ACTUATION WITHIN (SECONDS)
90
SUPERVISORY SIGNAL ACTUATION WITHIN (SECONDS)
200
TROUBLE SIGNAL ACTUATION WITHIN (SECONDS)
NEXT TEST PLUS 1 YEAR
TESTING RECORDS KEPT UNTIL
5 YEARS PLUS 1 YEAR
RESTORABLE, FIXED-TEMPERATURE, SPOT-TYPE HEAT DETECTORS: TESTING
RECORDS KEPT UNTIL
12 MONTHS
SUPERVISING STATION: TESTING RECORDS KEPT UNTIL