answered already passed
The state of a refrigerant leaving a refrigeration system's liquid receiver is:
a.) Low-Pressure Liquid
b.) Low-Pressure Gas
c.) High-Pressure Liquid
d.) High-Pressure Gas - correct answer ✔✔c.) High-Pressure Liquid
The refrigerant's pressure is constant leaving the refrigerant below the interface subcooled.
When the annualized leak rate reaches _____ or more, leaks in industrial process and
refrigeration units must be repaired with a 50-pound charge or larger.
a.) 40%
b.) 30%
c.) 10%
d.) 20% - correct answer ✔✔b.) 30%
EPA regulations require that all commercial and industrial process refrigeration containing more
than 50 lbs. of refrigerant must be repaired when the annual leak rate exceeds 30%. (Page19
ESCO EPA 9TH V2 Edition Prep Manual)
When evacuating a system, what is the minimum number of microns a vacuum pump must
pull?
, a.) 500000 Microns
b.) 50000 Microns
c.) 500 Microns
d.) 5000 Microns - correct answer ✔✔c.) 500 Microns
A finishing vacuum of 500 microns is acceptable for a new installation or a system being
serviced.
A high-pressure appliance with a capacity of less than 200 pounds. The level of an HCFC or HFC
refrigerant must be evacuated (recovered) to:
a.) 4 inches of vacuum
b.) 0 inches of vacuum
c.) 10 inches of vacuum
d.) 15 inches of vacuum - correct answer ✔✔b.) 0 inches of vacuum
A high-pressure appliance containing less than 200 lbs. of an HCFC or HFC refrigerant must be
evacuated (recovered) to a level of 0 inches of vacuum. (Page 20 ESCO EPA 9TH V2 Edition Prep
Manual)
Which of the following is commonly contained in refrigerants made before 1950?
a.) SO2
b.) HNO6
c.) NO2
d.) None of the above - correct answer ✔✔a.) SO2