Question:
What is the purpose of fire warning equipment?
Answer:
To provide a reliable means of notifying occupants of the presence of fire and of the need to
escape.
Question:
What are the 3 basic requirements for all devices?
Answer:
1. They must be approved and listed for the purposes for which they are intended
2. All devices will be installed according to manufacturers recommendations
3. The required minimum and location of detectors shall be satisfied.
Question:
What is the emergency evacuation signal that shall be used?
Answer:
ANSI S3.41, or American National Standard Emergency Evacuation Signal
,Question:
Can the emergency evacuation signal be used for other devices?
Yes, so long as those devices are used to indicate the need for evacuation
Answer:
Question:
When can fire warning equipment incorporate voice notification?
Answer:
When the voice message is completely contained within the 1.5 second pause of the emergency
evacuation signal.
When the voice message is first preceded by a minimum of 8 cycles of the emergency evacuation
signal
When the voice message interrupts the emergency evacuation signal for no longer than 10
seconds, and is followed by 2 cycles of the emergency evacuation signal.
Question:
Whose responsibility is it to inform a technician of occupants with hearing disabilities?
Answer:
The hearing impaired party
Question:
In what 6 places must detectors be installed to meet the requirements?
Answer:
1. In all sleeping and guest rooms
, 2. Outside of all sleeping rooms, within 21ft of the door
3. On every level, including basements
4. On every level of a residential board and care occupancy, including basements
5. In the living areas of a guest suite
6. In the living areas of a residential board and care occupancy
Question:
All points on a ceiling shall have a smoke alarm within a distance of _________ travel distance
or shall have the equivalent of ___________ smoke alarm per _________ meter squared
Answer:
• 9.1m (30ft)
• One
• 46.5m2 (500ft2)
Question:
In what 4 ways are smoke and heat alarms permitted to be powered?
Answer:
1. Commercial light and power supply capable of operating the device for at least 24 hours in
normal condition and 4 minutes of alarm
2. A noncommercial AC source with secondary power source capable of operating the device for
at least 7 days in the normal condition and 4 minutes of alarm.
3. A non rechargeable, non replaceable primary battery capable of operating the device for at
least 10 years and 4 minutes of alarm, followed by 7 days of trouble.
4. If battery primary power is permitted, requirements must meet 11.6.6 and 11.6.7