GOODFELLOW
BLOCK II
Dry pipe systems are hydrostatically tested every _____ years -
ANSWERS-Five
How often are private hydrants tested?? - ANSWERS-Annually
When flow testing a dry barrel, it must drain completely in no more than
how long? - ANSWERS-One hour
A critical feature and limitation of special agent fire, extinguishing
systems is the ______ and ______ quantity of available agent -
ANSWERS-Specific
Limited
Flammable liquid storage rooms
Dip tanks
Paint spray booths
END OF
PAGE
1
, FIRE INSPECTOR 2 LATEST
GOODFELLOW
BLOCK II
Fire extinguishing system would be used to protect these ? -
ANSWERS-Dry chemical fire extinguishing system
What are the four methods that foam extinguishes a fire? - ANSWERS-
Smothering
Cooling
Suppressing
Separating
When service testing and performing periodic inspections of detection
and Alarm systems, nickel-cadmium and sealed lead acid batteries are
inspected how often? - ANSWERS-Semi annually
What cannot be tested periodically because this would destroy the
detector? - ANSWERS-Nonrestorable fixed temperature detector
Hairdryers or electric heat guns can be used on this detector to
effectively and safely test it. Which detector is it? - ANSWERS-
Restorable heat detectors
END OF
PAGE
2
, FIRE INSPECTOR 2 LATEST
GOODFELLOW
BLOCK II
How often do you test restorable heat detection devices?? - ANSWERS-
Semi annually
How often do you check fusible link detectors with replaceable links? -
ANSWERS-Semi annually
For Central Station systems what do you test monthly? - ANSWERS-
Signaling equipment
For Central Station systems what three things do you test bimonthly? -
ANSWERS-Water flow indicators
Automatic fire, detection systems
Supervisory equipment
For Central Station systems what three things do you test semi annually?
- ANSWERS-Manual fire alarm devices
Water tank level devices
Other automatic sprinkler system supervisory devices
END OF
PAGE
3
, FIRE INSPECTOR 2 LATEST
GOODFELLOW
BLOCK II
For emergency Voice alarm systems, what do you test quarterly? -
ANSWERS-Functional test of various components
For emergency Voice alarm systems, what do you test annually? -
ANSWERS-All components
a small fire may be expected or some parts may be an ordinary hazard in
what type of occupancy? - ANSWERS-Light hazard occupancy
In what type of occupancy would you find moderate size incipient Fires
or fire growth that is probably within control of fire extinguishers if
discovered quickly? - ANSWERS-Ordinary hazard occupancy
And what type of occupancy would there be a high amount of
combustible material and flammable liquid or rapidly spreading fire, that
may develop? - ANSWERS-Extra hazard occupancy
Class A fire extinguishers have a maximum travel distance of how many
feet? - ANSWERS-75 feet
END OF
PAGE
4