UPDATED ACTUAL Exam Questions and
CORRECT Answers
According to CCR, Title 23 UST Regulations, What is the frequency that the Monitor
Certification must be performed? - CORRECT ANSWER - Every 12 Months
If visual monitoring is utilized as the means of release detection for single walled tank, it must be
conducted on a _______ Basis. - CORRECT ANSWER - Daily
The Purpose of spill and overfill protection equipment is to minimize the potential for a release
during: - CORRECT ANSWER - Fuel Deliveries
Which of the following is a potential symptom of toxic petroleum exposure: - CORRECT
ANSWER - Dizziness
Tremors
Eye irritation
All of the above(correct)
Under-Dispenser Containment is required for ______ underground storage tank systems -
CORRECT ANSWER - All
All of the following are true for Automatic Tank Gauging (ATG) except for: - CORRECT
ANSWER - ATG system are required to be installed in all UST system
According to CCR Title 23, UST regulations Spill containment (spill bucket) must meet all of
the following requirements except: - CORRECT ANSWER - Be installed on vent risers
Suction piping may not require leak detection if it has one check valve located where? -
CORRECT ANSWER - Directly below the suction pump
,Service Technician performing work on Monitoring equipment must be trained and certified by
__________ - CORRECT ANSWER - The manufacture of the equipment.
Air monitoring must be conducted ________ when performing work within a confined space. -
CORRECT ANSWER - Prior to and during
A UST Service Technician must be recertified by the equipment Manufacture at the time interval
recommended by the equipment manufacture or at least every ____ months, whichever is
greater. - CORRECT ANSWER - 36 Months
When an automatic tank gauge is utilized for single-walled tank leak detection, it shall test the
tank at least monthly after product delivery or when the tank is filled to within _____ percent of
the highest operating level during the previous month. - CORRECT ANSWER - 10
The following is true of spill buckets except: - CORRECT ANSWER - Must provide
drainage for spilled product into the secondary containment sump.
If during an inspection of dispensing equipment at a retail gas station you find that the product is
dispensing at a significant lower rate than usual. You should check: - CORRECT
ANSWER - For piping leaks.
According to CCR title 23, UST Regulations the local agency must be notified by the
Owner/Operator how long before conducting Secondary Containment Testing? - CORRECT
ANSWER - At least 48 hours before the test.
Poppet Valves are a Vapor Recovery Component installed: - CORRECT ANSWER - on
the vapor recovery riser
If equipped with an ATG it shall be programmed to test the tank _______? - CORRECT
ANSWER - at least monthly
, A Vacuum-assist nozzle is a component of a(n) ________? - CORRECT ANSWER -
Stage II vapor recovery system
Stage I Vapor Recovery can be installed in the following configured(s): - CORRECT
ANSWER - Dual Point, Manifold, & Coaxial
An Underground tank System includes: - CORRECT ANSWER - The underground
storage tank
Piping
Ancillary Equipment
All of the above is correct
If equipped with an overfill alarm, the alarm must be triggered to alert the delivery operator
when the tank is no more than _______ full. - CORRECT ANSWER - 90%
Approved Cathodic Protection Methodologies include: - CORRECT ANSWER -
Sacrificial Anodes, & Impressed current system
_________is a system for exchanging gasoline vapors in a storage tank(s) and product in a fuel
delivery truck. - CORRECT ANSWER - Stage I Recovery
Automatic Line Leak Detectors, installed on Underground Piping with Secondary Containment.
Shall be capable of detecting a leak of _______ at 10 PSI. - CORRECT ANSWER -3
gallons per hour (GPH)
The fastest exposure for Petroleum Toxicity to affect the body is through: - CORRECT
ANSWER - Inhalation (Through breathing)
According to California Health and Safety Code for Underground Storage of Hazardous
substances, An "underground storage tank" is defined as: - CORRECT ANSWER - An
underground tank and connecting piping.