100% CORRECT ANSWERS
Residential - ANSWER -570
Data Centers - ANSWER -942
Class 1 - ANSWER -Single building with one equipment room
Class 2 - ANSWER -Single building with multiple telecom spaces
Class 3 - ANSWER -Multiple buildings on a single campus
Class 4 - ANSWER -Multiple sites with multiple buildings
Labels - ANSWER -Consist of face stock material
Tags - ANSWER -Attached to the mounting surface
Electronic identifieres - ANSWER -Prevent potential intruders from identifying
the location of key components
What is the minimum bend radius for a 50 mm (2in) conduit? - ANSWER -12
inches
When installing optical fiber, consider placing three innerducts in a 103mm (4 trade
size) conduit with the following sizes: - ANSWER -two 38 mm (1.5in), one 25mm
(1in)
Open top cable supports should be installed to provide a minimum of
________________ clearance above ceilings - ANSWER -3 inches
PBB - ANSWER -dedicated extension of the building ac grounding (earthing)
, electrode system for the telecom bonding infrastructures
TBC - ANSWER -bonds the electrical systems grounding (earthing) electrode
system to the PBB
TBB - ANSWER -interconnects the PBB to the SBB
BBC - ANSWER -used to equalize potentials between SBBs on the same floor of
a structure.
Which is better for an "L" rating? High or Low Numbers - ANSWER -Low
F rating- how many hours - ANSWER -1-4 Hrs
T rating- how many hours - ANSWER -0-3 Hrs
Electric motors and transformers - ANSWER -48"
Fluorescent Lamps - ANSWER -6"
Arc Welders - ANSWER -31.5"
Frequency Induction Heating - ANSWER -39"
Which OLTS testing method stimulates the loss of two mated pairs and an
installed optical fiber link? - ANSWER -One jumper method
What can cause a gain splice on an OTDR trace? - ANSWER -Mismatch in the
fibers
L Rating - ANSWER -A firestops ability to provide a smoke stop. (air leakage
rate)
To avoid damaging cable jacket, how often must you securely fasten electrical
nonmetallic tubing (ENT) - ANSWER -3 Feet so it does not damage the cable What