NM ES-3 EXAM COMPLETE
QUESTIONS AND CORRECT
lo
DETAILED ANSWERS (VERIFIED
ANSWERS) A+ GRADED
yc
ud
St
, What is the minimum clearance to the edge of a wood stud for a wire hole?
1 1/4 inches(NEC 300.4 A 1)
What is the minimum separation between a class 1 fire alarm circuit conductor and a class 2 or
class 3 circuit?
1/4 inch
A basic alarm system will have __ power sources.
2
ck
What is the minimum required clearance between a receiving antenna and 250 volt line not
insulated?
2 Feet
lo
The minimum clearance for an antenna to other conductors is?
2 Feet (NEC 810.13)
yc
How far away must communications cables be from electric, light, or power conductors
2 inches
what is the maximum blink rate on a strobe light per second?
ud
2 (NFPA 72 18.5.2.1)
On a voice alarm system what is the minimum number of cycles it has to report an evacuation
procedure?
2 (NFPA 72 24.4.1.2.1)
St
What is the minimum required height for a propriety manual pull fire alarm?
3 1/2 feet or 42 inches
An overhead feeder must have a clearance of __ from chimneys, radio, and television antennas.
3 Feet (NEC 225.19 B)
The NEC classifies Continuous Load as equipment running at a maximum load of __ ____?