100% de satisfacción garantizada Inmediatamente disponible después del pago Tanto en línea como en PDF No estas atado a nada 4,6 TrustPilot
logo-home
Examen

609 ESCO 100% EXPERT VERIFIED CORRECT AND UPDATED 2025!

Puntuación
-
Vendido
-
Páginas
5
Grado
A+
Subido en
06-02-2025
Escrito en
2024/2025

609 ESCO 100% EXPERT VERIFIED CORRECT AND UPDATED 2025! Contaminated refrigerants must be handled with some extra precautions. If you are unsure about a refrigerant, EPA strongly recommends (but does not require) that technicians obtain a refrigerant identifier as a useful tool. When a technician encounters a "mystery" refrigerant, it must be recovered using a piece of equipment dedicated to this purpose. Unapproved refrigerants may contain a high percentage of flammable substances, such as propane or butane, and a fire hazard may result. Check with your equipment manufacturer to be sure the equipment has protection against risks of ignition. Once the refrigerant has been recovered, it must be properly stored and/or sent to a reclamation facility to be reclaimed or destroyed. Refrigerants From Non-Mobile Sources Refrigerant recovered from non-mobile sources, such as residential or commercial air conditioners or refrigeration systems may not be used in MVAC systems or reco --- correct answer ---page 5

Mostrar más Leer menos
Institución
609 ESCO
Grado
609 ESCO

Vista previa del contenido

609 ESCO 100% EXPERT VERIFIED CORRECT
AND UPDATED 2025!


Contaminated refrigerants must be handled with some extra precautions. If you
are unsure about a refrigerant, EPA strongly recommends (but does not require)
that technicians obtain a refrigerant identifier as a useful tool. When a technician
encounters a "mystery" refrigerant, it must be recovered using a piece of
equipment dedicated to this purpose. Unapproved refrigerants may contain a high
percentage of flammable substances, such as propane or butane, and a fire hazard
may result. Check with your equipment manufacturer to be sure the equipment has
protection against risks of ignition. Once the refrigerant has been recovered, it
must be properly stored and/or sent to a reclamation facility to be reclaimed or
destroyed. Refrigerants From Non-Mobile Sources Refrigerant recovered from non-
mobile sources, such as residential or commercial air conditioners or refrigeration
systems may not be used in MVAC systems or reco --- correct answer ---page 5




HFO-1234yf The Hydro Fluoro Olefin Refrigerant HFO-1234yf was developed
through a joint project between Chemours (Formally DuPont) and Honeywell. HFO-
1234yf is expected to become the preferred global alternative refrigerant candidate
for automotive OEM applications and the aftermarket. HFO-1234yf has a GWP of 4
and an ODP of zero. HFO-1234yf has a cooling capacity that is comparable to HFC-
134a and is compatible with HFC-134a components. Furthermore, this refrigerant
does have a flammability factor, which will need to be addressed prior to its
adoption as a substitute for HFC-134a. Recovery Cylinders Recovery cylinders
differ in many ways from disposable cylinders. A disposable cylinder such as those
used for new product, are not refillable and MUST NEVER be used for recovery.
Recovery cylinders are specifically designed to be refilled. Recovery cylinders have
at least two ports, one vapor and one liquid. The EPA is --- correct answer ---page
6

, Manifold Gauge Set When servicing a system with a manifold gauge set, the high,
low, and center hoses must have shut off valves within 12 inches (30 cm) of the
service ends. Shut off valves can be manually operated or close automatically when
the hose is removed. During all service operations, the shut off valves should be
closed until connected to the system or the charging source to prevent the
introduction of air and to contain rather than vent any refrigerant. When the gauge
set is removed from the vehicle or charging source, it must be connected to the
recovery equipment to recover the refrigerant from the hoses. Recycling
Requirements Approved recycling equipment must meet all of the criteria that
recovery only equipment must meet. In addition, recycling equipment must clean
the used refrigerant to the minimum purity level as defined in SAE standards
before it can be used in a motor vehicle air conditioning sys --- correct answer ---7




When using an electronic leak detector, always follow the manufacturer's
operating instructions. In addition to the manufacturer's instructions, the
following should be observed: 1. Always leak test with the engine off. 2. Only, a
small amount of refrigerant is required to perform a leak test. A gauge reading of
50 psi is all that is needed. At temperatures below 50°F., leaks may not be
measurable, since 50 psi may not be attainable. 3. To avoid contaminating the tip
of your leak detector, remove excessive dirt from suspected leak areas. Do not use
cleaners or solvents, your detector may be sensitive to their ingredients. 4.
Visually inspect the system, and look for signs of air conditioning oil leakage,
damage, and corrosion on all lines, hoses, and components. Each suspected area
should be carefully checked. 5. Follow the system around in a continuous path to
ensure that no areas are missed. If a leak is found, con --- correct answer ---page 8




concerning the issue of leak repairs. 7 Proper Charging and Recharging of MVAC
Systems After system evacuation, and dehydration the system can be charged with

Escuela, estudio y materia

Institución
609 ESCO
Grado
609 ESCO

Información del documento

Subido en
6 de febrero de 2025
Número de páginas
5
Escrito en
2024/2025
Tipo
Examen
Contiene
Preguntas y respuestas

Temas

$11.49
Accede al documento completo:

100% de satisfacción garantizada
Inmediatamente disponible después del pago
Tanto en línea como en PDF
No estas atado a nada

Conoce al vendedor

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
PASSINGMASTER01 Chamberlain College Of Nursing
Seguir Necesitas iniciar sesión para seguir a otros usuarios o asignaturas
Vendido
460
Miembro desde
4 año
Número de seguidores
333
Documentos
2804
Última venta
5 horas hace
TIGHT DEADLINE? I CAN HELP Many students don't have the time to work on their academic papers due to balancing with other responsibilities, for example, part-time work. I can relate. kindly don't hesitate to contact me, my study guides, notes and exams

QUALITY DOCUMENTS FOR BEST RESULTS. In my page you will find latest Exams ,Assignments, Test Banks, Exam Elaboration, test with Questions and Answers, Discussions, Case Studies, package deals, etc. I upload quality. Instant delivery.

3.7

42 reseñas

5
21
4
6
3
5
2
3
1
7

Recientemente visto por ti

Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes