and Correct Answers
what is the rule regarding motors and transformers then an equipment / Telecom room
✔️✔️Telecom cable must be kept 48 inch away from the motors and transformers
all incoming conduit and innerduct should include ✔️✔️firestopping
on a riser subsystem all conduit should be ✔️✔️raised and pushed on each end and have no
more than two 90-degree bends between pull points or pull boxes
any penetrations through walls or floors that we are required for the riser pathways must
✔️✔️be neatly sleeved and fire stopped immediately upon completing the penetration
if trays or wire ways are shared, the power and Telecom cables must ✔️✔️be separated by a
grounded metallic barrier
the support structure for horizontal subsystems consist of ✔️✔️j hooks, bags, and bridle rings,
ladder racks / trays
all patch cables must be installed with a service loop of ✔️✔️18 inches in the field