FDNY Z51 RMO Set Test Questions And Verified Correct Solutions | Updated . What can a clogged pump strainer cause? - ANSWER : A reduction or loss in water flow which will lead to high condenser head pressure. What part of the Refrigeration system is the solenoid valve part of? - ANSWER : The pump down cycle (Thermostat - Solenoid Valve - Low Pressure Controller). What is the proper machine start up procedure? - ANSWER : Check oil, start chilled water pump, start condenser water pump, start tower fans and start up machine. How does a reciprocating machine cycle compressors on and off? - ANSWER : Through the use of the low pressure control. What refrigerant has the best Refrigeration effect and highest latent heat? - ANSWER : Ammonia (R-717) / ASHRE Classification is B2. What is the leaving water temperature of an induced draft cooling tower that is operating efficiently? - ANSWER : At some temperature between the dry and wet bulb temperature. What could a sudden reduction in the supply flow of the cooling tower water result in? - ANSWER : An increase in head pressure. How do reciprocating compressor unloaders operate? - ANSWER : By keeping the compressor suction valves open.