LP Gas Master Qualifier: Regulators & Line Sizing Questions and Answers Already Passed
LP Gas Master Qualifier: Regulators & Line Sizing Questions and Answers Already Passed What is the working pressure in an aboveground tank at 90 degrees Fahrenheit? A. 149 B. 153 C. 165 D. 174 C. 165 How many BTU's per hour will a 120 AG tank produce with 30% Liquid and at 40 degrees Fahrenheit? A. 316,740 B. 332,640 C. 366,140 D. 398,240 B. 332,640 If using Methanol how much should be added to a 500 Gallon Tank? A. 3 pints B. 4 pints C. 5 pints D. 6 pints C. 5 pints What is the Maximum Lock Up pressure of a Second Stage Regulator? A. 120 % of Operating Pressure B. 130 % of Operating Pressure C. 140 % of Operating Pressure D. 150 % of Operating Pressure B. 130 % of Operating Pressure How many inches of Water Column are there in 1 pound of LP gas pressure? A. 24.92 B. 25.45 C. 26.89 D. 27.67 D. 27.67