Class A/B Operator for Underground Storage Tank Exam 2023 with complete solution
The Class A and Class B certification must be renewed every: Ans 5 years UST financial responsibility requirements apply to what? Ans 600 gallon used oil tank Secondary Containment is required for what? Ans New UST Systems, Piping in contact with the ground, and Replacement UST A Class A operator shall maintain the records of UST site inspections for a *minimum* of: Ans 3 years New owners of an existing UST system shall register the UST system with DEQ/LARA within what period from date of ownership? Ans 30 days UST systems with cathodic protection should be inspected for proper operation by a qualified cathodic protection tester on the following schedule: Ans Every three years UST systems with impressed current cathodic protection systems must be inspected at a minimum: Ans Every 60 days Within what period after a repair should a cathodically protected UST system be tested to ensure it is working properly? Ans 6 months Pressurized underground piping that routinely contains regulated substances shall be monitored for releases in a manner that meets what requirements? Ans Be equipped with a line leak detector, and have an annual line tightness testA suspected release must be confirmed to the DEQ/L
Escuela, estudio y materia
- Institución
- Class A/B Operator for Underground Storage Tank
- Grado
- Class A/B Operator for Underground Storage Tank
Información del documento
- Subido en
- 8 de marzo de 2024
- Número de páginas
- 9
- Escrito en
- 2023/2024
- Tipo
- Examen
- Contiene
- Preguntas y respuestas
Temas
-
class ab operator for underground storage tank ex