The operable part of a manually actuated alarm initiating device shall be not less than ____ inches AFF. <<Ans>> 42 inches Consider the use of grounding electrodes. Rod and pipe electrodes shall not be less than____ feet in length? <<Ans>> 8 feet Smoke detectors should not be located in a direct airflow or closer than ____ inches from an air supply diffuser or return air opening? <<Ans>> 36 inches Consider the use of visible notification appliances. Wall mounted appliances shall be mounted such that the entire lens is not less than ____ inches above the finished floor? <<Ans>> 80 inches How many 16 gauge conductors are permitted in a 4 x 1 1/2 inches square box? <<Ans>> 12 Wall mounted audible appliances shall have their tops above the finished floors at heights of not less than ____ inches and below the finished ceilings at distances of not less than 6 inches? <<Ans>> 90 inches A minimum ____ db ambient sound level with a 6 hour exposure time requires hearing protection? <<Ans>> 92 db Spot type heat sensing fire detectors shall be located on the ceiling not less than ____ inches from the sidewall. <<Ans>> 4 inches While operating an aerial lift, the use of a body harnes and ____ is not required? <<Ans>> Stabilizer Hook, Grounding Pole, Insulation Mat Spot type smoke detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and ____ inches down from the ceiling to the top of the detector. <<Ans>> 12 inches The distance between spot type heat detectors shall not exceed their listed spacing, and there shall be detectors within a distance of ____ the listed spacing, measured at right angles from the walls? <<Ans>> One Half Where partitions extend to within ____ percent of the ceiling height, the spaces separated by the partitions shall be considered as separate rooms? <<Ans>> 15 percent Consider 1,000 feet total of 18 gauge soild coated copper at 167o Fahrenheit. The resistance of this conductor is ____ ohm? <<Ans>> 8.08 ohm Consider the installation of heat detectors on a ceiling with beams. A ceiling shall be treated as a smooth ceiling if the beams project no more than____ inches below the ceiling? <<Ans>> 4 inches Which of the following conductor types is an acceptable substitute for FPLR? <<Ans>> FPLP, CMP Consider the use of PLFA fire alarm cable. The size of conductors in multiconductor cable shall not be smaller than____ AWG? <<Ans>> 26 AWG You are using a power tool that has a 3 prong (grounded) plug. The only outlets available are 2 prong (non grounded). What can be done? <<Ans>> Locate a 3 prong plug or used a tool with a 2 prong plug. The power source for a power limited fire alarm circuit shall be a listed PLFA or Class ____ transformer? <<Ans>> Class 3 transformer Which of the following is a symptom of heat stroke? <<Ans>> Red skin, Elevated Body Temperature, Rapid, Weak pulse The maximum number of 14 AWG, RHH conductors permitted in 1/2 inch EMT is ____? <<Ans>> 4 The distance between smoke detectors shall not exceed a nominal spacing of ____ feet? <<Ans>> 30 feet A portable ladder shall support at least ____ times the maximum intended load. <<Ans>> 3.3 times Consider smoke detector placement on a peaked ceiling. Detectors shall first be spaced and located within ___ feet. of the peak, measured horizontally? <<Ans>> 3 feet Ladders must be inspected____ to identify any visible defects that could cause employee injury? <<Ans>> Before initial use Consider heat detectors with listed spacing of 50 feet placed on a smooth and flat ceiling which is 10 feet AFF. Based on this ceiling height, the heat detectors shall have a spacing of ____ feet between devices? <<Ans>> 50 feet If a door release detector is specifically listed for door frame mounting, or if a listed combination or integral detector door closer assembly is used ____ detectors shall be required if installed according to the manufacturers published instructions? <<Ans>> 1 detector

Mostrar más Leer menos
Institución
NICET Level 1 Fire Alarm Systems
Grado
NICET Level 1 Fire Alarm Systems









Ups! No podemos cargar tu documento ahora. Inténtalo de nuevo o contacta con soporte.

Escuela, estudio y materia

Institución
NICET Level 1 Fire Alarm Systems
Grado
NICET Level 1 Fire Alarm Systems

Información del documento

Subido en
19 de julio de 2023
Número de páginas
10
Escrito en
2022/2023
Tipo
Examen
Contiene
Preguntas y respuestas

Temas

Vista previa del contenido

NICETLevel1FireAlarmSystemsExamQuestionAnd
AnswersAlreadyPassed
Theoperablepartofamanuallyactuatedalarminitiatingdeviceshallbenotless
than____inchesAFF.<<Ans>>42inches
Considertheuseofgroundingelectrodes.Rodandpipeelectrodesshallnotbeless
than____feetinlength?<<Ans>>8feet
Smokedetectorsshouldnotbelocatedinadirectairfloworcloserthan____inches
fromanairsupplydiffuserorreturnairopening?<<Ans>>36inches
Considertheuseofvisiblenotificationappliances.Wallmountedappliancesshallbe
mountedsuchthattheentirelensisnotlessthan____inchesabovethefinished
floor?<<Ans>>80inches
Howmany16gaugeconductorsarepermittedina4x11/2inchessquarebox?
<<Ans>>12
Wallmountedaudibleappliancesshallhavetheirtopsabovethefinishedfloorsat
heightsofnotlessthan____inchesandbelowthefinishedceilingsatdistancesof
notlessthan6inches?<<Ans>>90inches
Aminimum____dbambientsoundlevelwitha6hourexposuretimerequires
hearingprotection?<<Ans>>92db
Spottypeheatsensingfiredetectorsshallbelocatedontheceilingnotlessthan
____inchesfromthesidewall.<<Ans>>4inches
Whileoperatinganaeriallift,theuseofabodyharnesand____isnotrequired?
<<Ans>>StabilizerHook,GroundingPole,InsulationMat
Spottypesmokedetectorsshallbelocatedontheceilingor,ifonasidewall,
betweentheceilingand____inchesdownfromtheceilingtothetopofthedetector.
<<Ans>>12inches
Thedistancebetweenspottypeheatdetectorsshallnotexceedtheirlistedspacing,
andthereshallbedetectorswithinadistanceof____thelistedspacing,measured
atrightanglesfromthewalls?<<Ans>>OneHalf
Wherepartitionsextendtowithin____percentoftheceilingheight,thespaces
separatedbythepartitionsshallbeconsideredasseparaterooms?<<Ans>>15
percent Consider1,000feettotalof18gaugesoildcoatedcopperat167oFahrenheit.The
resistanceofthisconductoris____ohm?<<Ans>>8.08ohm
Considertheinstallationofheatdetectorsonaceilingwithbeams.Aceilingshallbe
treatedasasmoothceilingifthebeamsprojectnomorethan____inchesbelowthe
ceiling?<<Ans>>4inches
WhichofthefollowingconductortypesisanacceptablesubstituteforFPLR?
<<Ans>>FPLP,CMP
ConsidertheuseofPLFAfirealarmcable.Thesizeofconductorsinmulticonductor
cableshallnotbesmallerthan____AWG?<<Ans>>26AWG
Youareusingapowertoolthathasa3prong(grounded)plug.Theonlyoutlets
availableare2prong(nongrounded).Whatcanbedone?<<Ans>>Locatea3
prongplugorusedatoolwitha2prongplug.
ThepowersourceforapowerlimitedfirealarmcircuitshallbealistedPLFAorClass
____transformer?<<Ans>>Class3transformer
Whichofthefollowingisasymptomofheatstroke?<<Ans>>Redskin,Elevated
BodyTemperature,Rapid,Weakpulse
Themaximumnumberof14AWG,RHHconductorspermittedin1/2inchEMTis
____?<<Ans>>4
Thedistancebetweensmokedetectorsshallnotexceedanominalspacingof____
feet?<<Ans>>30feet
Aportableladdershallsupportatleast____timesthemaximumintendedload.
<<Ans>>3.3times
Considersmokedetectorplacementonapeakedceiling.Detectorsshallfirstbe
spacedandlocatedwithin___feet.ofthepeak,measuredhorizontally?<<Ans>>3
feet
Laddersmustbeinspected____toidentifyanyvisibledefectsthatcouldcause
employeeinjury?<<Ans>>Beforeinitialuse
Considerheatdetectorswithlistedspacingof50feetplacedonasmoothandflat
ceilingwhichis10feetAFF.Basedonthisceilingheight,theheatdetectorsshall
haveaspacingof____feetbetweendevices?<<Ans>>50feet
Ifadoorreleasedetectorisspecificallylistedfordoorframemounting,orifalisted
combinationorintegraldetectordoorcloserassemblyisused____detectorsshall
berequiredifinstalledaccordingtothemanufacturerspublishedinstructions?
<<Ans>>1detector
$10.49
Accede al documento completo:

100% de satisfacción garantizada
Inmediatamente disponible después del pago
Tanto en línea como en PDF
No estas atado a nada

Conoce al vendedor
Seller avatar
jerry95parker
5.0
(1)

Conoce al vendedor

Seller avatar
jerry95parker University of the People
Seguir Necesitas iniciar sesión para seguir a otros usuarios o asignaturas
Vendido
2
Miembro desde
2 año
Número de seguidores
1
Documentos
74
Última venta
11 meses hace

5.0

1 reseñas

5
1
4
0
3
0
2
0
1
0

Recientemente visto por ti

Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes