Study guide for Electrical Apprenticeship Year 1 covering essential NEC code provisions and electrical installation standards. Topics include meter categories, raceway and conduit provisions, grounding and bonding requirements, service drop clearances, device box calculations, and load calculations for residential and commercial applications. This Q&A formatted guide is ideal for apprentices preparing for exams and practical assessments, with direct references to NEC tables and code sections.

Vista previa del contenido

Electrical Apprenticeship Year 1




Telecommunications and electronic equipment - ANSWER-Category 1 meters are rated
for _______________.

residential current - ANSWER-Category 2 meters are rated for _______________.

industrial purposes - ANSWER-Category 3 meters are rated for _______________.

three-phase utility and outdoor conductors - ANSWER-Category 4 meters are rated for
_______________.


The length of a straight pull for multiple raceways must be at least ____ times the trade
size (metric designator) of the largest single raceway. - ANSWER-eight

Conduit pro isions - ANSWER-chapter 9 table 4
v




Raceway Pro isions - ANSWER-Table 348.22
v




ENT shall be secured e ery - ANSWER-3 feet (362.30 A)
v




Contact of dissimilar metals (except for the combination of aluminum and steel) should
be a oided where er possible to lessen the potential for ____. - ANSWER-gal anic action
v v v




Grounding conductors are required for circuits o er ____ amperes. (When using Flexible
v



Metal Conduit) - ANSWER-20

An indi idual branch circuit ____. - ANSWER-supplies only one utilization equipment
v




As required by 110.26, working space around electrical equipment is primarily
concerned with ____. - ANSWER-ser ice and escape due to emergency
v




A 12 AWG copper conductor requires ____ free space within a de ice box. - ANSWER-
v



2,25 in. cubed

, Each yoke or strap containing one or more de ices or equipment in a de ice box counts
v v



as ____ conductor(s). - ANSWER-two

Concealed means ____ by the building structure or finish. - ANSWER-rendered
inaccessible

For a one-family dwelling, at least one receptacle outlet accessible while standing at
grade le el and located not more than _____ft. abo e grade shall be installed at the front
v v



and back of the dwelling. - ANSWER-6.5

At least one 125- olt, single phase, 15- or 20-ampere-rated receptacle outlet shall be
v



installed within _______ ft of the electrical ser ice equipment in a multifamily dwelling. -
v



ANSWER-25

Minimum clothes dryer demand load - ANSWER-5000 watts 220.54

Load Calculations - ANSWER-idk, mang

Ser ice drop conductors shall ha e a ertical clearance of not less than _____________
v v v



feet abo e the roof surface - ANSWER-8
v




Equipment grounding conductor pro isions - ANSWER-Table 250.122 and 250.102
v




What is the ser ice demand load in kW for an apartment complex containing ten each of
v



the following. 15 kW ranges, 13 kW ranges, 11 kW ranges, and 9 kW ranges. the ser ice v



is single phase. - ANSWER-Table 220.55
First find the a erage kW using 12 kW for any range rated less than 12 kW
v



(10 x 15) + (10 x 13) + (10 x 12) + (10 x 12) = 150 + 130 + 120 + 120 = 520 kW
[Note that we used 12 kW for the 11kW and the 9 kW]
520 kW / 40 ranges = 13 kW a erage range size.
v



Column C shows 15kw + 40 (number of ranges) = 55 kW
This 55kW must be increased by 5% for each kW abo e 12 the a erage size is.
v v



55 kW x 1.05 = 57.75 kW demand load.

In_________________, remote, central, or automatic control of lighting shall be
permitted - ANSWER-hallways, staircases, and outdoor entrances

A grounded circuit conductor shall be permitted to ground non-current carrying metal
parts of equipment on the ______________ side of the ac ser ice disconnecting means -
v



ANSWER-supply

Equipment grounding conductors, where installed, shall be increased in size
proportionately according to________________ - ANSWER-Circular mil area of the
ungrounded conductors

Información del documento

Subido en
4 de agosto de 2026
Número de páginas
8
Escrito en
2026/2027
Tipo
Examen
Contiene
Preguntas y respuestas
$16.80

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Vendido
0
Seguidores
0
Artículos
35
Última venta
-



Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes