Which source shall NOT be used to power the venturri of a WAGD system? - ANSWERSmedical air Which type of connectors shall connect the medical air compressors with their intake and outlet piping? - ANSWERSflexible Continuing to use an existing system that is noncompliany with the requirements of this code shall be permitted unless the _______ has determined that such use poses a distinct hazard to life. - ANSWERSauthority having jurisdiction Cylinder and cryogenic liquid container outlet connections shall be designed as to render the attachment point ________ when removal of the outlet connection is attempted. - ANSWERSunusable Which of the following systems shall not be permitted to be located in an outdoor enclosure? - ANSWERSmedical air compressor sources What is required of the alarm system if another alarm condition occurs while the audible alarm is manually silenced? - ANSWERSRe-initiation of the audible signal Cylinders in use and in storage shall be prevented from reaching temperatures in excess of ____________. - ANSWERS125ºF Mechanical exhaust for central supply locations shall not be more than ____. - ANSWERS500 cfm For purposes of this code, an oxygen enriched atmosphere is an atmosphere where to total concentration of oxygen exceeds _______ by volume. - ANSWERS23.5% Locations for central supply systems shall have electrical devices protected from ___________. - ANSWERSphysical damage

Vista previa del contenido

Med Gas Mock Exam Questions With
All Correct Detalied Answers
Which source shall NOT be used to power the venturri of a WAGD system? -
ANSWERSmedical air

Which type of connectors shall connect the medical air compressors with their intake
and outlet piping? - ANSWERSflexible

Continuing to use an existing system that is noncompliany with the requirements of this
code shall be permitted unless the _______ has determined that such use poses a
distinct hazard to life. - ANSWERSauthority having jurisdiction

Cylinder and cryogenic liquid container outlet connections shall be designed as to
render the attachment point ________ when removal of the outlet connection is
attempted. - ANSWERSunusable

Which of the following systems shall not be permitted to be located in an outdoor
enclosure? - ANSWERSmedical air compressor sources

What is required of the alarm system if another alarm condition occurs while the audible
alarm is manually silenced? - ANSWERSRe-initiation of the audible signal

Cylinders in use and in storage shall be prevented from reaching temperatures in
excess of ____________. - ANSWERS125ºF

Mechanical exhaust for central supply locations shall not be more than ____. -
ANSWERS500 cfm

For purposes of this code, an oxygen enriched atmosphere is an atmosphere where to
total concentration of oxygen exceeds _______ by volume. - ANSWERS23.5%

Locations for central supply systems shall have electrical devices protected from
___________. - ANSWERSphysical damage

Final line pressure regulators, when used for cryogenic fluid central supply systems
shall be of a ________ design. - ANSWERSbalanced

The pressure in the main line of each medical gas system, the operation and condition
of the source of supply and the reserve source (if any) shall be monitored at the
_______ alarm - ANSWERSmaster

, The instrument air dew point high alarm from each compressor site will indicate at the
master alarm panels when the line pressure dew point is greater than _______. -
ANSWERS-22ºF

Bulk nitrous oxide system consists of more than _________ of gas. - ANSWERS3,200
lb

Brazed joints shall be made using a brazing alloy that exhibits a melting temperature in
excess of _________ to retain the integrity of the piping system in the event of fire. -
ANSWERS1000ºF

Manifolds for gas cylinders shall consist of ______ equal headers; each with one
average day's supply, but not fewer than _______ connections. - ANSWERStwo - two

Manifolds for gas cylinders shall actuate a(n) ___________ signal and shall activate an
indicator at all _______ alarm panels to indicate when or just before changeover from
one header to the other. - ANSWERSlocal - master

In a medical gas system with emergency reserve, which alarm system(s) will activate
when, or just before, the changeover to the reserve supply occurs? - ANSWERSmaster

The gas produced by evaporation from the secondary header in a cryogenic liquid
container system shall enter the supply system __________ of the final line regulator. -
ANSWERSupstream

A facility is in the planning stages of installing an emergency oxygen supply connection
(EOSC). Which of these components are required at this connection? - ANSWERS4
alarm connection points to monitor the truck

A(n) ___________ can be used as a substitute for the EOSC at a category 1 facility. -
ANSWERSin-building emergency reserve

Final line pressure controls shall be sized to ___ of the peak calculated demand. -
ANSWERS100%

Cryogenic fluid central supply systems up to the source valve, shall be installed in
accordance with ______. - ANSWERSNFPA 55

Central supply systems for nitrous oxide and carbon dioxide using cylinders or portable
containers shall be prevented from reaching temperatures lower than ___°F. -
ANSWERS20

Installers of Category 1 medical gas piping systems must be qualified to ASSE 6010.
What is the certification requirement for installers of a Category 3 system? -
ANSWERS6010

Información del documento

Subido en
4 de agosto de 2026
Número de páginas
11
Escrito en
2026/2027
Tipo
Examen
Contiene
Preguntas y respuestas
$12.79

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Vendido
4
Seguidores
0
Artículos
1474
Última venta
1 semana hace


Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes