California CSLB C10 Electrical Exam UPDATED ACTUAL QUESTIONS
AND CORRECT ANSWERS
Question 1: According to NEC Chapter 9, Table 1, what is the maximum
percentage fill allowed for a conduit or tubing containing three or more
distinct electrical conductors or cables?
• A) 31%
• B) 40%
• C) 53%
• D) 60%
Correct Answer: B
Rationale: For conduits containing 3 or more conductors, the maximum
allowable cross-sectional fill percentage is 40% per NEC Chapter 9 Table
1.
Question 2: Under California Contractors State License Board (CSLB)
rules, what is the current bond amount required for a C-10 Electrical
Contractor's bond?
• A) $7,500
• B) $12,500
• C) $15,000
• D) $25,000
Correct Answer: C

,Rationale: The CSLB requires all active licensee classifications, including
C-10 electrical contractors, to maintain a contractor's bond in the
amount of $15,000.
Question 3: Under Cal/OSHA construction safety orders, at what height
is fall protection mandatory for general construction work?
• A) 4 feet
• B) 6 feet
• C) 10 feet
• D) 15 feet
Correct Answer: B
Rationale: Cal/OSHA Title 8 mandates fall protection for employees
working on surfaces with an unprotected side or edge 6 feet or more
above a lower level.
Question 4: What is the standard working space depth required in front
of electrical equipment operating at 600 volts or less (nominal) with
exposed live parts on one side and grounded parts on the other
(Condition 2), per NEC 110.26?
• A) 2.5 feet
• B) 3.0 feet
• C) 3.5 feet
• D) 4.0 feet
Correct Answer: C

,Rationale: Condition 2 of NEC 110.26(A)(1) requires a clear working
space depth of 3.5 feet for systems operating up to 150 volts to ground,
increasing for higher voltages.
Question 5: According to California Business and Professions Code 7159,
what is the maximum down payment allowed by law for a home
improvement contract?
• A) 20% of the total contract price or $2,500, whichever is less
• B) 10% of the total contract price or $1,000, whichever is less
• C) 50% of the total contract price upfront before materials are
ordered
• D) There is no statutory limit on down payments in California.
Correct Answer: B
Rationale: California law restricts home improvement contract down
payments to a maximum of 10% of the total contract price or $1,000,
whichever is less.
Question 6: What is the maximum distance allowed between supports
for Type NM (Romex) cable according to NEC Article 334?
• A) Every 3 feet, and within 8 inches of boxes
• B) Every 4.5 feet, and within 12 inches of boxes
• C) Every 6 feet, and within 12 inches of boxes
• D) Every 10 feet, and within 36 inches of boxes
Correct Answer: B

, Rationale: NEC 334.30 requires Type NM cable to be supported and
secured at intervals not exceeding 4.5 feet and within 12 inches of
every outlet box, cabinet, or fitting.
Question 7: In a commercial dwelling unit or residential kitchen, GFCI
protection is required by NEC Article 210.8 for all 15- and 20-ampere,
125-volt receptacles installed in which location?
• A) Bathrooms only
• B) Bathrooms, kitchens, and rooftops
• C) Bathrooms, kitchens, rooftops, outdoors, and within 6 feet of
the outside edge of a sink
• D) All indoor areas regardless of sink proximity
Correct Answer: C
Rationale: NEC 210.8 expands GFCI requirements to include bathrooms,
kitchens, rooftops, outdoors, and indoor areas within 6 feet of sinks.
Question 8: Under NEC Article 250, what is the minimum size grounding
electrode conductor (GEC) required when connecting to a concrete-
encased electrode (Ufer ground) made of reinforcing steel, regardless of
the size of the service-entrance conductors?
• A) 8 AWG copper
• B) 6 AWG copper
• C) 4 AWG copper
• D) 2 AWG copper
Correct Answer: B

Información del documento

Subido en
28 de julio de 2026
Número de páginas
52
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$20.49

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
CreativeWrites
3.6
(21)
Vendido
87
Seguidores
3
Artículos
7656
Última venta
1 día hace


Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes