QUESTIONS AND ANSWERS
(VERIFIED ANSWERS) | LATEST
(2026/2027) UPDATED VERSION |
100% GUARANTEED PASS
{JUST RELEASED}
1. Operating devices shall operate at - ANSWER ✓ 32F to 120F
2. Manual actuators shall not have a force more than - ANSWER ✓ 40lbs
3. Manual actuators shall not have a movement of more than - ANSWER ✓ 14
inches
4. Instructions with pictographs and lettering shall be atleast - ANSWER ✓ 1/4
inches
5. Pipe and fittings shall be made of - ANSWER ✓ Non combustible materials
, 6. galvanized pipe and fittings - ANSWER ✓ Shall not be used
7. During assembly examine pipe - ANSWER ✓ Internally to detect and remove
contaminants
8. Readily acces means for manual actuators - ANSWER ✓ Shall be located in a
path of egress
9. Manual actuators shall be installed - ANSWER ✓ No more than 48in and no
less than 42in
10. Fusible links shall be located - ANSWER ✓ At above each cooking appliance
11. Fusible links shall be - ANSWER ✓ 12 in in front of said item
12. A test shall be used on pipe using - ANSWER ✓ Nitrogen or dry air not
exceeding normal operating pressure
13. Piping shall not - ANSWER ✓ Be hydrostatic tested
14. Owners inspection - ANSWER ✓ Monthly