The length of an unlisted outside plant cable should be limited to _____ feet. -
ANSWER-50 feet
A primary protector should be located as close as practicable to where the cable
enters the building. -ANSWER-True
With a primary protector installed inside a building, the communications wires
should enter the building through? -ANSWER-A noncombustible insulating
bushing (or a metal raceway)
Raceways or bushing that enter a building should be? -ANSWER-Sloped upward
from the outside or a service loop made
Whenever practicable, a distance of ____ feet or more should be maintained
between communications wires and lighting conductors. -ANSWER-6 feet
Only plastic splice cases may be used as enclosures for terminating telephone
cables. -ANSWER-False
Cables and conductors of Class 3 circuits should not be placed in. a cable
compartment with conductors of non - power -limited fire alarm circuits. -
ANSWER-True
,The bonding conductors for use with the primary protector should never be
smaller than _______ AWG. -ANSWER-14 AWG
Secondary protectors on those circuits exposed to possible accidental contact
with electric light conductors _____ Volts to ground should be used with primary
protectors. -ANSWER-300+ Volts
Whenever there is lightning exposure, the interbuilding circuit must be
protected? -ANSWER-By a listed protector on each end
An area with an average of _____ or less thunderstorm days a year plus an earth
resistivity of fewer than ______ ohmmeters is not considered to have lightning
exposure. -ANSWER-5/100 ohmmeters
The fire alarm circuit disconnect should be designed in such a way that it can be
secured in the "on" position. -ANSWER-True
Concerning fire alarm systems, the overcurrent protection should not exceed
_________ amperes for 18 AWG conductors. -ANSWER-7 amperes
The location of the branch-circuit overcurrent protective device for supplying fire
alarm equipments must be permanently identified at the fire alarm control unit. -
ANSWER-True
The fire alarm circuit disconnecting means should have _______ identification. -
ANSWER-Red
, The power source off non- power limited fire alarm circuits should have an output
voltage no larger than _______ volts nominal -ANSWER-600 volts
The branch circuits for supplying fire alarm equipment is normally allowed to
supply other loads? -ANSWER-False
Power -supply and fire alarm circuits conductors may stay in the same cable as
long as? -ANSWER-They are connected to the same equipment.
Only metallic terminal boxes may be used as enclosures for splicing telephone
cables. -ANSWER-False
You can only use copper conductors for fire alarm systems. -ANSWER-True
The proper size of conductors in a multi conductors cable should be at least. -
ANSWER-26 AWG
The proper size of single conductors should be at least? -ANSWER-18 AWG
A cable that is low smoke-producing should exhibit a max peak optical density of
no more than? -ANSWER-0.5
Direct -buried cables that are emerging from the ground must be protected by
enclosures or other means. -ANSWER-True