What is the minimum standpipe riser protection? - ANSWER- Risers
and laterals of Class I standpipe systems not located within an exterior
exit shall be protected by a degree of fire resistance equal to that
required for vertical enclosures in the building in which they are located,
IFC and IBC 905.4.1
What is the proper clearance for marine motor fuel dispensing location?
- ANSWER- 50 feet, IFC 2310.5.5
The area surrounding an outdoor storage area or tank shall be kept clear
of combustible materials and vegetation for a minimum distance of? -
ANSWER- 25 ft, IFC 5004.11
What is the minimum piping systems and testing for flammable and
combustible liquids? - ANSWER- Unless tested in accordance with
ASME B31.9, piping before being covered enclosed or placed in use
shall be hydrostatically tested to 150%........ IFC 5703.6.3
When are plans required for LP-gas? - ANSWER- Single container
2,000 gallon. Aggregate 4,000 gallons IFC 6101.3
, 2|Page
When is fire detection required for Class III commodity in high piled
storage? - ANSWER- 501 square feet, IFC Table 3206.2
What is the minimum door width for occupant load of 200? - ANSWER-
40 inches, 200 x 0.2, IFC and IBC 1005.3.2
In a Group B, what is the occupant load required to install a fire alarm
system? - ANSWER- 500, IFC and IBC 907.2.2
What is the travel distance to an exit for a nonsprinklered F2 occupancy?
- ANSWER- 300, IFC and IBC Table 1017.2
What is the width of stairways for an occupant load of 40? - ANSWER-
36 inches, IFC and IBC 1011.2 Exception 1
What is the type of protection required for rooftop heliports? -
ANSWER- Foam protection, IFC 2007.6
When is a permit needed for medical gas? - ANSWER- 504 cubic feet,
IFC Table 105.6.8 Oxidizing
A restaurant and bar are located on the 5th floor of hotel with 150 units
on the floor, how many visual and notification appliances are required? -
ANSWER- 12, IFC and IBC Table 907.5.2.3.2