The power output of the source of Class 1 Remote - Control and Signaling Circuit. -
ANSWER-Class 1 Remote - Control and Signaling Circuits are NOT required to be
limited
Class 1 circuit conductors and power - supply conductors that are not functionally
associated? -ANSWER-They should be separated by a solid fixed barrier.
Class 1 circuit may occupy the same cable as long as? -ANSWER-(AC or DC does
not matter) As long as all conductors are insulated for the mex voltage of any
conductor in the same cable.
Class 1 and Class 2 circuit should be identified at terminal and junction location. -
ANSWER-True
Overcurrent protection should never exceed ______ amperes for 18 AWG
conductors? -ANSWER-7 amperes
Class 1 circuits conductors are normally allowed to be tapped? -ANSWER-True
,Overcurrent protection should never exceed _______ amperes for 16 AWG. -
ANSWER-10 amperes
Class 1 circuits and power - supply circuits may stay in the same raceway if? -
ANSWER-If the equipment powered is functionally associated
Supply service drops of max 750 volts that run parallel to communications service
drops should posses a minimum separation of ______ inches at any point along
the span. -ANSWER-12 inches
talking about the definition of Imax. -ANSWER-Refers to the max output current
under any noncapacitive load - this definition does not exclude short circuit.
Cables and conductors of Class 2 circuits may be placed in a cable compartment
with conductors of non- power -limited fire alarm circuits. -ANSWER-False
The length of an unlisted outside plant cable should be limited to _____ feet. -
ANSWER-50 feet
A primary protector should be located as close as practicable to where the cable
enters the building. -ANSWER-True
With a primary protector installed inside a building, the communications wires
should enter the building through? -ANSWER-A noncombustible insulating
bushing (or a metal raceway)
Raceways or bushing that enter a building should be? -ANSWER-Sloped upward
from the outside or a service loop made
, Whenever practicable, a distance of ____ feet or more should be maintained
between communications wires and lighting conductors. -ANSWER-6 feet
Only plastic splice cases may be used as enclosures for terminating telephone
cables. -ANSWER-False
Cables and conductors of Class 3 circuits should not be placed in. a cable
compartment with conductors of non - power -limited fire alarm circuits. -
ANSWER-True
The bonding conductors for use with the primary protector should never be
smaller than _______ AWG. -ANSWER-14 AWG
Secondary protectors on those circuits exposed to possible accidental contact
with electric light conductors _____ Volts to ground should be used with primary
protectors. -ANSWER-300+ Volts
Whenever there is lightning exposure, the interbuilding circuit must be
protected? -ANSWER-By a listed protector on each end
An area with an average of _____ or less thunderstorm days a year plus an earth
resistivity of fewer than ______ ohmmeters is not considered to have lightning
exposure. -ANSWER-5/100 ohmmeters
The fire alarm circuit disconnect should be designed in such a way that it can be
secured in the "on" position. -ANSWER-True