GUARANTEED
All torch operators, an oxigen-fuel torch using any amount of oxigen and flamable gas and
fire guards must have a current - CORRECT ANSWER -Certificate of Fitness
The Certificate of Fitness holder - CORRECT ANSWER -must regulate the pressure and
flow of oxygen and natural gas to each torch.
if the torch operator for jewelry manufacture involves - CORRECT ANSWER -any oxygen
with any fuel gas containers, the operator must be a C of F holder.
A Certificate of Fitness Holder must keep his or her certificate - CORRECT ANSWER -on
their person or otherwise readily available for inspection by any representative of the fire
Department
The easiest way to extinguish a fire caused by a leak is to - CORRECT ANSWER -close the
shutoff valve
Permits issued by the FDNY are required to conduct the following hot work: - CORRECT
ANSWER -storing, using or handling oxygen and a flammable gas, storing, using or
handling any flammable gas (e.g. LPG or CNG or acetylene) in excess of
400 SCF. Storing, using or handling any oxidizing gas (e.g. oxygen) in excess of 504 SCF.
For LPG, 400 SCF is - CORRECT ANSWER -approximately 47 lbs
, the number of LPG containers for the storage, use, handling or transportation, requiring a
permit - CORRECT ANSWER -14.1 oz = 54 cont.
16.4 oz = 46 cont.
20 lbs = 3 cont.
33.5 lbs = 2 cont.
40 lbs = 2 cont.
100 lbs = 1 cont.
Portable LPG containers that are more than 16.4 oz and CNG containers with a capacity
greater than 8.7 SCF - CORRECT ANSWER -must NOT stored, handled, or used indoors in
the following occupancies (as defined in the Building code): residential occupancies, factory
and industrial occupancies; educational occupancies; institutional occupancies, except as the
commissioner may authorize by rule.
Site-specific permit - CORRECT ANSWER -may be a permanent permit or a temporary
permit. Permanent permits are valid for 12 months only
A city-wide permit is valid - CORRECT ANSWER -up to 30 days
Permits shall be - CORRECT ANSWER -readily available on the premise for inspection by
Fire Department representatives.
Hot work authorization should be issued by the responsible person, and it - CORRECT
ANSWER -must be available for inspection by any representative of the department during
the performance of the work, and for 48 hours after the work is complete
FDNY permits - CORRECT ANSWER -will be posted in a central location and recorded in a
log book to assist in the coordination of construction related activities.