Answers | GRADED A+ | LATEST UPDATE 2026/2027 |
100% ASSURED PASS.
WAGD networks shall provide a WAGD inlet in all locations where __________ is
intended to be administered.
a. Nitrogen
b. Medical Air
c. Nitrous Oxide
d. Oxygen
c. Nitrous Oxide
Audible and visual alarm indicators shall meet which of the following
requirements?
a. Individual indicators shall NOT be less than DN20 size
b. Testing to determine indicator function should be scheduled periodically and
records maintained between testing.
c. CGA C-7
d. The staff should be trained to operate the test button periodically and report
malfunctions.
b. Testing to determine indicator function should be scheduled periodically and records
maintained between testing.
,Which of the following systems shall not be permitted to be located in an outdoor
enclosure?
a. Bulk cryogenic liquid systems
b. Manifolds for gas cylinders
c. Manifolds for cryogenic liquid containers
d. Medical air compressor sources
d. Medical air compressor sources
NFPA 99 requires tubing to be cut square using a sharp tubing cutter that shall be
free from grease, oil or other lubricants not suitable for oxygen service. What sort
of treatment is permitted of the tube ends before brazing?
a. May be reamed
b. May be deburred or rolled smooth
c. May be re-cleaned
d. none of the above
b. May be deburred or rolled smooth
,Thank you for Purchasing this exam
Study Guide. We provide high-quality
academic materials to help students
excel in exams. Our other Services
include but not limited to: academic
research, University & College
assignments writing, essay writing,
Online Classes, and research
projects. Our services are reliable,
affordable, and plagiarism-free. All
the Best in your Exam. For more
information; Contact us at:
or
0R
+254 741484450
, With the approval of the authority having jurisdiction, in what areas shall the
shutoff valves be permitted to be secured to prevent inappropriate access?
a.critical care
b.psychiatric or pediatric
c.maternity
d.anesthetizing
b. psychiatric or pediatric
For purposes of this code, an oxygen enriched atmosphere is an atmosphere
where to total concentration of oxygen exceeds _______ by volume. a.23.5%
b. 23.6%
c. 19.5%
d.93%
a.23.5%
Compressed gas cylinders must meet which of the following criteria in order to
be acceptable for use in an acute health care facility?
a.Be appropriately identified by labels or stencils in accordance with CGA C-7
criteria
b.Be appropriately color coded in accordance with U.S.D.A. requirements
c.Be constructed in accordance with specifications and regulations of OSHA
d.Utilize gas specific CGA connections
a. Be appropriately identified by labels or stencils in accordance with CGA C-7 criteria