DISPENSING INSTALLATION &
MAINTENANCE
The=point=of=transfer=at=a=dispensing=unit=must=be=____=from=Public=ways,=including=
public=streets,=highways,=thoroughfares,=and=sidewalks.
A.=10=feet
B.=15=feet
C.=25=feet=-=ans-✔✔A.=10=feet
Steel=supports=on=vertical=ASME=containers=shall=be=protected=against=fire=exposure=
with=a=material=having=a=fire=resistance=rating=of=a=least=_____,=except=that=continuou
s=steel=skirts=that=have=only=one=opening=that=is=18=in.=or=less=in=diameter=shall=have
=fire=protection=applied=to=the=______=of=the=skirts.
A.=3=hrs;=outside
B.=2=hrs;=outside
C.=3=hrs;=inside=-=ans-✔✔B.=2=hrs;=outside
Pressure=relief=devices=installed=in=underground=containers=serving=dispensing=syste
ms=shall=be=piped=vertically=upward=to=a=point=at=least=_____=above=the=ground.
A.=2=feet
B.=6=feet
C.=10=feet=-=ans-✔✔C.=10=feet
A=remote=emergency=shut=off=device=for=either=the=internal=valve=or=emergency=shutof
f=valve=is=required=to=be=located=not=less=than=_____=or=more=than=_____=from=the=li
quid=transfer=point.
A.=10=ft=;=50ft
B.=10=ft;=100ft
C.=3=ft;=100ft=-=ans-✔✔C.=3=ft;=100ft
The=markings=for=the=switch=or=circuit=breaker=to=shut=off=power=in=an=emergency=sha
ll=be=visible=from=________.