What is the minimum branch circuit size for a Level II EVSE with a 32-
ampere current rating?
Select one:
a.32 A
b.35 A
c.40 A
d.55 A - CORRECT ANSWER-c.40 A
32 A × 1.25 = 40 A minimum OCPD
What is the minimum size XHHW-
2 copper conductor permitted to supply a Level II EVSE that has a 30-
ampere current rating, assuming 75° terminations?
Select one:
a.12 AWG
b.10 AWG
c.8 AWG
d.6 AWG - CORRECT ANSWER-c.8 AWG
30 A × 1.25 = 37.5 A = 8 AWG
When calculating the voltage drop on a conductor of a given length, the following values m
ust be considered: conductor material, conductor length, and conductor operating temperat
ure.
Select one:
, True
False - CORRECT ANSWER-True
Calculate the voltage drop on a single-
phase circuit with 32 amperes of load, a distance of 320 feet from the load to the panelbo
ard, and served by 8 AWG copper THHN conductors.
Select one:
a.13 V
b.14 V
c.15 V
d.16 V - CORRECT ANSWER-d.16 V
2KIL / A = VD(2) × 12.9 × 32A × 320' / 16,510 cmil = 16 V
Calculate the following correct copper conductor size so that the branch circuit has a maxim
um voltage drop of 2%. The load on the circuit is 32 amperes, the distance from the load t
o the panelboard is 400 feet, and the circuit is 208 volts, single-phase.
a.3 AWG
b.1 AWG
c.1/0 AWG
d.250 kcmil - CORRECT ANSWER-b.1 AWG
2% × 208 V = 4.16 V
2 KIL / VD = A
2 × 12.9 × 32 A × 400' / 4.16 V =