1. What is the minimum burial depth for rigid metal conduit (RMC) under a
residential driveway according to NEC guidelines?
A. 6 inches
B. 12 inches
C. 18 inches
D. 24 inches
✔ Correct Answer: C. 18 inches
Explanation: NEC Table 300.5 specifies minimum cover requirements; for
RMC under driveways, 18 inches is required for adequate protection.
2. A continuous load is defined as a load where the maximum current is
expected to continue for how long?
A. 1 hour or more
B. 2 hours or more
C. 3 hours or more
D. 4 hours or more
✔ Correct Answer: C. 3 hours or more
Explanation: NEC defines a continuous load as one expected to run for 3
hours or more, impacting conductor and overcurrent sizing.
3. What is the required ampacity adjustment factor for 4 current-carrying
conductors in a raceway?
A. 100%
, B. 90%
C. 80%
D. 70%
✔ Correct Answer: C. 80%
Explanation: NEC Table 310.15(C)(1) requires an 80% adjustment factor for
4–6 current-carrying conductors.
4. Which conductor type is permitted for direct burial without conduit?
A. THHN
B. UF
C. NM
D. SE
✔ Correct Answer: B. UF
Explanation: Underground Feeder (UF) cable is specifically listed for direct
burial applications.
5. What is the minimum size copper grounding electrode conductor for a 200A
service?
A. #8 AWG
B. #6 AWG
C. #4 AWG
D. #2 AWG
✔ Correct Answer: B. #6 AWG
Explanation: NEC Table 250.66 specifies #6 copper for grounding electrode
conductor for 200A services.
6. In a dwelling unit, what is the minimum number of small appliance branch
circuits required?
A. One
B. Two
C. Three
D. Four
✔ Correct Answer: B. Two
, Explanation: NEC requires at least two 20-amp small appliance circuits for
kitchen/dining areas.
7. A 20A circuit using #12 AWG copper wire has a voltage of 120V. What is the
maximum load in watts?
A. 1,200 W
B. 2,000 W
C. 2,400 W
D. 2,800 W
✔ Correct Answer: C. 2,400 W
Explanation: Power = Voltage × Current = 120V × 20A = 2400W.
8. What is the maximum number of 90-degree bends allowed between pull
points in a conduit run?
A. Two
B. Three
C. Four
D. Five
✔ Correct Answer: C. Four
Explanation: NEC limits conduit bends to 360 degrees total between pull
points.
9. Which device protects against ground-fault shock hazards?
A. AFCI
B. GFCI
C. Fuse
D. Breaker
✔ Correct Answer: B. GFCI
Explanation: Ground-Fault Circuit Interrupters detect imbalance and shut
off power quickly.
10.What is the minimum working clearance in front of electrical panels up to
150V to ground?
A. 24 inches