1. What alarm system is used to monitor the operation of the source supply of each
medical gas and vacuum piping system - Correct Answer: Master alarm system
2. What guide is for preparation of precautionary labeling and marking of compressed gas
containers - Correct Answer: CGA C-7
3. A system of non-interchangeable medical gas and vacuum connectors shall comply with
________for low pressure connections for medical gas applications. - Correct
Answer: CGA V-5 Diameter index safety system
4. A warning system within an area uses a _____that provides continuous visible and
audible surveillance of category 1 and catgegory 2 medical gas and vacuum systems -
Correct Answer: Area Alarm
5. An active system or equipment whose failure is not likely to cause injury to patients, staff
or visitors shall be designed to meet what category? - Correct Answer: 3
,6. All pressure relief valves shall be made of brass, bronze or _____ - Correct Answer:
Stainless steel
7. Cylinders in use and in storage shall be prevented from reaching temperatures in excess
of _____ - Correct Answer: 125F
8. Manifolds in this category shall have a _____signal that visibly indicates the operating
status of the equipment and shall activate an indicator at all _____alarm panels to
indicate when or just before changeover from one header to the other. - Correct
Answer: Local - Master
9. Nitrous Oxide and carbon dioxide using cylinders or portable containers shall be
prevented from reaching temperatures lower than _____ - Correct Answer: 20F
10. The gas produced by evaporation from the secondary header in a cryogenic liquid
cylinder system shall enter the supply system _____ of the final line regulator -
Correct Answer: Upstream
11. The reserve header in a cryogenic liquid cylinder system shall have sufficient gas cylinder
connections for an average day's supply, but not fewer than ______ connections -
Correct Answer: 3
12. Dew point shall activate the required alarms when the dew point at system pressure
exceeds _____ - Correct Answer: 35F
13. Liquid ring compressor system shall have a reserve medical air standby head (1hour) or a
______ - Correct Answer: Compressor
, 14. Liquid ring compressors, service water and seal water shall be treated to control _____ -
Correct Answer: Waterborne pathogens and Chlorine
15. Medical air compressor systems shall have a pressure relief valve set at _____ percent
above line pressure - Correct Answer: 50%
16. Medical air compressors that are designed to separate the oil-containing section from
the compression chamber shall be provided with a coalescing filter with a _____ -
Correct Answer: Element change indicator
17. Medical air filters shall be located immediately upstream of the _____ - Correct
Answer: Final line regulator
18. Medical air filters shall be sized for 100% of the system peak calculated demand and be
rated for a minimum of _____efficiency at _______ micron or greater? - Correct
Answer: 98% @ 1
19. Medical air shall be sampled at _____NPS valved sample port upstream of the final line
pressure regulator - Correct Answer: 1/4"
20. Medical air sources shall be used only for _____. - Correct Answer: Human
respiratory applications
21. The compressor air intakes shall be located outdoors at a minimum distance of _____
above the ground - Correct Answer: 20'
22. Where medical air piping systems at different operating pressures are required, the
piping shall separate after the ______ ? - Correct Answer: filters