Which organization publishes standards specifically for bulk oxygen
systems - ANSWER - NFPA
When testing a sprinkler system how much time is allowed between
achieving sustained flow and initiation of fire alarms - ANSWER - 90
seconds
Which agency publishes general standards on storing hazardous or
flammable materials - ANSWER - NFPA
What is the appropriate way to detect suspected gas cylinder leaks -
ANSWER - using soapy water
OSHA and the Uniform Fire Code (UFC) define class 1 flammable
liquids as any liquid with a flash point below what temperature -
ANSWER - 73 degrees Fahrenheit
What organization addresses safety signs and color-code schemes -
ANSWER - ANSI
pg. 1
,What fire-related injury contributes to the most fire deaths - ANSWER -
Smoke Inhalation
What NFPA publication addresses electrical grounding requirements in
healthcare facilities - ANSWER - NFPA 99
What NFPA standard addresses the installation of fire sprinkler systems -
ANSWER - NFPA 13
What standard or law requires healthcare facilities to develop
evacuation/egress procedures for disabled persons - ANSWER - ADA
Title III
Firewatch must be implemented when a SPRINKLER System is out of
service for more than ___ hours in a 24 hour period - ANSWER - 10
Firewatch must be implemented when a FIRE ALARM system is out of
service for more than ___ hours in a 24 hour period - ANSWER - 4
What standard addresses the requirement for testing roof hatches -
ANSWER - NFPA 72
How often do standpipe hoses need to be fully inspected
(according to NFPA 1962) - ANSWER - Every 3 Years
Which NFPA standard addresses the placement of smoke detectors in
corridors - ANSWER - NFPA 72
pg. 2
,What NFPA publication contains detailed information about the
maintenance of (non-stored) emergency power systems? - ANSWER -
NFPA 110
Occupancy separations, such as one for business, are permitted provided
the services are separated by a ____ hour separation. - ANSWER - 2
How often must the BBI and PFI of the statement of conditions be
updated to meet Joint Commission requirements? - ANSWER - BBI=
annually and PFIs are no longer allowed. The Safer Matrix is the new
norm and See It Cite It is the program motto.
How often must organizations conduct fire drills in patient care areas
(assuming there is no construction or ILSMs)? - ANSWER - Once per
shift per quarter
At what frequency must a temporary but equivalent fire alarm system be
tested when in operation? - ANSWER - Monthly
How often should an organization inspect fire/smoke walls from exterior
to exterior? - ANSWER - Annually
How many stories must a building have before the placement of floor
identification is mandatory? - ANSWER - 5
How often are smoke dampers required to be tested in a hospital
occupancy? - ANSWER - 1 year after installation and every 6 years
thereafter
pg. 3
, How often are smoke dampers required to be tested in a business
occupancy (including remote outpatient centers)? - ANSWER - 1 year
after installation and every 4 years thereafter
What is the minimum width of an exit (door) and passageway serving as
a means of egress from a patient care area? - ANSWER - 44 inches
When considering egress, what's the maximum length of dead-end
corridors in new buildings? - ANSWER - 75 feet
How often must facility-maintained fire hydrants be checked? -
ANSWER - Annually
What document does the Joint Commission Emergency Management
(EM) standard require hospitals to develop to address prioritized
emergency response procedures? - ANSWER - Emergency Operations
Plan (or EOP more commonly)
What agency published the "Hospital Evacuation Decision Guide?" -
ANSWER - Federal Emergency Management Agency (FEMA)
What statement accurately describes the Joint Commission requirement
for [load bank] testing emergency generators? - ANSWER - Once every
36 months for a minimum of four hours
When is annual load testing of generators required? - ANSWER - When
the generators are not tested monthly under minimum 30% load