Questions with Answers.
Is this statement true or false? Fiberglass and flexible plastic piping do not need to have
cathodic protection. - Answer False.
Cathodic protection - Answer a technique used to control the corrosion of a metal surface by
making it the cathode of an electrochemical cell. A simple method of protection connects the
metal to be protected to a more easily corroded "sacrificial metal" to act as the anode.
Fill in the blank to make the statement correct. Owners and Operators must keep the most
recent ___ records of cathodic protection testing. - Answer 2
How long do owners and operators have to report a release to the implementing agency? -
Answer 24 Hours
Fill in the blank if the tank was installed on or before April 11, 2016 manual tank gauging ALONE
can be used on tanks containing ________ gallons and meeting certain diameter requirements?
- Answer 1000 gallons or less.
True or False?
Tanks from 1001 gallons to 2000 gallons and tanks from 551 and 1000 gallons that do not meet
the specified diameters can temporarily use manual tank gauging when it is combined with tank
tightness testing. - Answer True
True or False?
Under UST regulation combining manual tank testing and tank tightness testing can only be
used for 10 years after the tank was installed and may not be used for any tanks installed after
April 11 2016. - Answer True
True or False?
Manual tank gauging can be used to meet the release detection monitoring requirements for
any size of tank. - Answer False
True or False?
Owners and operators may cancel a financial responsibility mechanism at any time. - Answer
False
, When can an owner or operator cancel a financial responsibility mechanism? Only when they
have obtained an alternative mechanism; the tank has been permanently closed or undergoes a
change in service; or if corrective action is required and completed. - Answer Only when they
have obtained an alternative mechanism; the tank has been permanently closed or undergoes a
change in service; or if corrective action is required and completed.
True or False?
Owners and operators do not need to maintain financial responsibility once the UST has been
permanently closed. - Answer True
True or false?
Septic tanks are regulated by the 40 CFR part 280. - Answer False
Owners and operators who switch from E10 to E15 have 30 days AFTER switching to notify the
implementing agency. - Answer False
They have 30 days BEFORE
Which of the following substances if stored in an
UST would cause the UST to be regulated under 40 CFR part 280? Choose all that apply:
-Gasoline with 10% ethanol
-Propane
-Diesel
-Kerosene - Answer gasoline with 10% ethanol, diesel, and kerosene.
How long do owners and operators keep records demonstrating compatibility with gasoline
containing 15% ethanol? - Answer As long as the UST system stores 15% ethanol
True or false?
Only tanks need to be compatible with the regulated substances stored. - Answer False
True or false? Under-dispenser containment used for piping interstitial monitoring does not
have to be tested for tightness once every three years. - Answer False
True or false?
Double walled spill buckets where the space between the walls of the spill bucket is no longer
monitored at least every 30 days must be tested for liquid tightness within -1 year after
monitoring ceases-. - Answer False. within 30 days