1



MEDICAL GAS 6010 INSTALLERS
Practice Test Exam Questions with
100% Correct Answers Latest
Version Top Rated
An existing system that is not in strict compliance with the
provisions of this code shall be permitted to be continued in
use as long as the _ has determined that such use does not
constitute a distinct hazard to life. A) architect B) authority
having jurisdiction C) engineer D) nursing staff
B) authority having jurisdiction
Cylinder and cryogenic liquid container outlet connections
shall be designed as to render the attachment point _ when
removal of the outlet connection is attempted. A) reusable B)
unusable C) unsuitable D) universal
B) unusable
Cylinders in use and in storage shall be prevented from
reaching temperatures in excess of _ *F. A) 120 B) 125 C) 130
D) 135
B) 125
Nitrous oxide and carbon dioxide using cylinders or portable
containers shall be prevented from reaching temperatures
lower than _ *F A) 130 B)125 C) 20 D) -20
C)20
Which of the following systems shall not be permitted to be
located in an outdoor enclosure? A) bulk cryogenic liquid
cylinders B) manifolds for gas cylinders C) manifolds for
cryogenic liquid containers D) medical air sources

,2



D) medical air sources
Indoor locations for oxygen, nitrous oxide, and mixtures of
these gases shall not communicate with any of the following
except _? A) area with open flames B) designated storage
area C) engines D) kitchens
B) designated storage area
Locations for central supply systems shall have _ devices
protected from physical damage? A) electrical B) pressure
indicating C) regulating D) relief
A) electrical
Outdoor locations surrounded by impermeable walls, except
fire barrier walls, shall have protected ventilation openings at
the _ of each wall to allow free circulation of air within the
enclosure? A) base B) corner) C) middle D) top
A) base
All positive pressure supply systems shall be provided with
duplex line pressure regulators piped in _? A) circuit B) loop
C) parallel D) series
C) parallel
All pressure relief valves shall be made of brass, bronze, or
_? A) carbon steel B) cast iron C) copper D) stainless steel
D) stainless steel
Central supply systems for positive pressure gases shall
have one or more relief valves, the valves shall have a relief
setting that is _% above normal working operating pressure?
A) 30 B) 40 C) 50 D) 60
C) 50
When vented to the outside, relief valve vent lines shall be
labeled in which way? A) adhesive markers B) any manner
that will distinguish them from the medical gas pipeline C)
stenciling D) stickers

, 3



B) any manner that will distinguish them from the medical gas
pipeline
An auxiliary source connection shall consist of all of the
following except? A) removable plug or cap B) tee C) valve D)
visual pressure indicator
D) visual pressure indicator
In central supply systems using gas or liquid cylinders, each
header shall have a _ to prevent debris from entering the
manifold controls? A) check valve B) filter C) monitor D)
relief valve
B) filter
Manifolds for gas cylinders shall consist of two equal
headers, each with enough cylinders for an average day's
supply, but not fewer than _ connections? A) 5 B) 4 C) 3 D) 2
D) 2
Manifolds for gas cylinders shall have a(n) _ signal that
visibly indicates the operating status of the equipment and
shall activate an indicator at all master alarm panels when or
just before changeover from one header to the other takes
place? A) area B) master C) local D) zone
C) local
When multiple buildings are served from a single cryogenic
liquid oxygen source, it is required to place the emergency
oxygen supply connection in _ ? A) each building served B)
the building closest to the source C) the largest building
served D) the main building only
A) each building served
The minimum clearance around EOSC for a temporary
source of supply is _ ft? A) 2 B) 3 C) 5 D) 6
B) 3

Información del documento

Subido en
2 de febrero de 2026
Número de páginas
27
Escrito en
2025/2026
Tipo
Examen
Contiene
Preguntas y respuestas
$13.99

¿Documento equivocado? Cámbialo gratis Dentro de los 14 días posteriores a la compra y antes de descargarlo, puedes elegir otro documento. Puedes gastar el importe de nuevo.
Escrito por estudiantes que aprobaron
Inmediatamente disponible después del pago
Leer en línea o como PDF

Seller avatar
Los indicadores de reputación están sujetos a la cantidad de artículos vendidos por una tarifa y las reseñas que ha recibido por esos documentos. Hay tres niveles: Bronce, Plata y Oro. Cuanto mayor reputación, más podrás confiar en la calidad del trabajo del vendedor.
KGeorge
3.6
(35)
Vendido
178
Seguidores
25
Artículos
4783
Última venta
3 días hace


Por qué los estudiantes eligen Stuvia

Creado por compañeros estudiantes, verificado por reseñas

Calidad en la que puedes confiar: escrito por estudiantes que aprobaron y evaluado por otros que han usado estos resúmenes.

¿No estás satisfecho? Elige otro documento

¡No te preocupes! Puedes elegir directamente otro documento que se ajuste mejor a lo que buscas.

Paga como quieras, empieza a estudiar al instante

Sin suscripción, sin compromisos. Paga como estés acostumbrado con tarjeta de crédito y descarga tu documento PDF inmediatamente.

Student with book image

“Comprado, descargado y aprobado. Así de fácil puede ser.”

Alisha Student

Preguntas frecuentes