QUESTIONS AND SOLUTIONS RATED A+
✔✔Given that a "Classified Area" is a located where a fire and explosion hazard exists
due to the presence of fuel vapors. Because vapors are heavier than air In a Class I,
Division 2 area, where may vapors be present - ✔✔Extending 20 feet from dispensers
to a height of 1.5 feet above ground
✔✔absorbent pads, and absorbent boom, fuel absorbet material - ✔✔When responding
to Fuel Spills, it is advisable to have the following equipment.
✔✔In accordance with PEI RP-500, a Level II Qualified Person may not perform what
duty? - ✔✔Replace a Healy VP1000 Pump
✔✔Volatile Organic Compounds - ✔✔VOC's
✔✔What does a Combustible-Gas Detector check for in Vapor Recovery Systems? -
✔✔Leaks/Vapors in Vapor Recovery Systems {or LELor LFL 10% max)
✔✔8.0 +- 2.0, The P/V Cap has a black sticker with gold letters stating these
positive/negative specs: - ✔✔3.0 +- 0.5
✔✔This is what connecting above ground vent lines together is called. - ✔✔Manifolding
✔✔Continuous monitoring which includes pressure (hydrostatic), vacuum in brine, was
required after July 1, 2004 for which station components? - ✔✔Sumps and UDCs
✔✔The Healy VPl000 runs at a higher RPM under what circumstances? - ✔✔When
both sides are activated and nozzles are removed from the dispenser
✔✔Where is the Vapor valve located at? - ✔✔Under the dispenser (nozzle is second
choice if dispenser is not available)
✔✔When installing a ball float vent valve, what type of sealant shall you use? - ✔✔A
gasoline resistant compound
✔✔After a maintenance repair, the GDF maintenance log requires the following
information - ✔✔Telephone number, name of tech/ repairman and date of maintenance/
test failure
✔✔Not considered piping - ✔✔Coaxial hose
✔✔Gasoline is rated __ in the NFPA category for flammability: - ✔✔3
, ✔✔Equalizes static electricity. Creates conductive connection between two entities
(Such as UST & tank truck). - ✔✔Bonding
✔✔Diverts static electricity into earth. Eliminates static buildup. - ✔✔Grounding
✔✔The Minimum level of Oxygen for a safe entry into a confined space shall be no less
than what percentage? - ✔✔19.5%
✔✔The first physical signs of Oxygen depletion exposure are what? - ✔✔Respiration
and heartbeat acceleration
✔✔any space or enclosure that has limited opening for entry and exit and may have
limited ventilation. - ✔✔A Confined Space
✔✔not considered confined space. - ✔✔Sump bucket
✔✔The most quickest route petroleum products may enter the body is: - ✔✔Inhalation
✔✔Short term, high-level exposure, effects are usually immediate · - ✔✔Acute
Exposure
✔✔Long term, low level exposure, effects may take years to appear - ✔✔Chronic
Exposure
✔✔All of the following types of PPE are approved by OSHA, Except - ✔✔Safety Can
✔✔Inverted coaxial hoses are used for what type of systems. - ✔✔Vacuum Assist
✔✔Stage 1 Vapor Recovery Systems are the transfer of Vapors from __________ to
___________. - ✔✔From UST to fuel delivery truck
✔✔Secondary containment testing must be completed by by ____ months after a new
installation or upgrade. - ✔✔6
✔✔Automatic line leak detectors shall be installed on underground pressurized piping
and be capable to detect a 3-gallon per hour leak rate at 10 psi within 1 hour, with a
probability of detection of at least ___? - ✔✔95%
✔✔Stage II Vapor Recovery Systems are the transfer of vapors from _________ to
_________. - ✔✔Vehicle Tank to UST