S-12 CITYWIDE SPRINKLER SYSTEMS,
S12 sprinkler Test Exam Questions and
Answers 100% Pass
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE
QUALIFICATIONS. - ANS OWNER
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF
__________ YEARS. - ANS 3
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS. -
ANS IMPAIRMENT COORDINATOR
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE
CONSIDERED PLANNED REMOVAL FROM SERVICE. - ANS 1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED
OUT OF SERVICE CONDITIONS. - ANS 1
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE
WITHIN ______ HOURS. - ANS 8
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT
CONDITION TO THE ___________ AND THE FIRE DEPT. - ANS OWNER OF THE BUILDING
, ©THESTAR 2025 ALL RIGHTS RESERVED
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL
BE CONSIDERED AN IMPAIRMENT. - ANS 30
WHAT DOES "OOS" STAND FOR? - ANS OUT OF SERVICE
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS.
CONTROL VALVES, AND FIRE COMMAND CENTER - ANS TAGS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL
VALVES. - ANS MASTER FIRE SUPPRESSION PIPING CONTRACTOR
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES
BEFORE AND AFTER. - ANS DRAIN TEST RESULTS
GREEN TAGS INDICATE THAT __________. - ANS NO IMPAIRMENT WAS FOUND
GREEN TAGS WILL BE PLACED ON THE ____________. - ANS MAIN CONTROL VALVE
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON
THE MAIN CONTROL VALVE. - ANS RED
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE
SYSTEM IS FULLY OUT OF SERVICE. - ANS WHITE
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM
IS PARTIALLY OUT OF SERVICE. - ANS BLUE
, ©THESTAR 2025 ALL RIGHTS RESERVED
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL STATION
AND OCCUPANTS. - ANS INSURANCE
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT NECESSARY
TESTS AND INSPECTIONS ARE CONDUCTED. - ANS IMPAIRMENT COORDINATOR
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN
________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING. - ANS 50, 40
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE
____________. - ANS MAIN CONTROL VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT. THESE
ARE TO BE MAINTAINED ON SITE FOR 3 YEARS. - ANS RECORDS
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT
PROCEEDINGS. - ANS REVOCATION
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE
FOLLOWING CERTS: - ANS REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE
OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER
SYSTEMS. - ANS MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH
_________ SPRINKLER HEADS OR LESS. - ANS 30
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS ARE
INSTALLED. - ANS 96