1. Installation factors that influence the strength of the adhesive anchor bond
include:
- Correct Answer: drilling of the hole following MPII
cleaning of the hole following MPII
injecting the adhesive following the MPII
2. Adhesive should be stored at: - Correct Answer: As directed by the MPII
3. Gel time is? - Correct Answer: 1. the amount of time between first
mixing the adhesive and when it becomes a noon-flowing material
2. increased when the temperature of the concrete are colder
3. decreased when the temperatures of the concrete are warmer
4. Powers 1000+ epoxy adhesive anchors must be installed in accordance
with: - Correct Answer: The MPII
5. ACI 355.4-11 applies to anchors with diameters of 1/4 or larger and an
embedment depth not exceeding: - Correct Answer: 20d
,6. The (?) ensures that the components are well mixed so the adhesive resin is
activated by the hardener - Correct Answer: Mixing nozzle
7. The ICC-ESR for the Powers 1000+ product specifies that holes drilled in
concrete be cleaned out using a: - Correct Answer: Steel wire brush
8. ACI 355.4 requires the manufacturer to provide inspection procedures for
each type of anchoring system, to verify proper usage of their products
(T/F) - Correct Answer: True
9. An observant inspector can derive clues about the quality of the
installations from tell-tale signs at the site of the installations which can
include: - Correct Answer: Packaging from non-specified adhesives,
discarded modified mixing nozzles, and lack of evidence of laying dedication
beads when opening a new cartridge
10.The ICC-ESR for the Powers 1000+ product requires that drilled holes for
threaded rod diameters greater than 3/4 be cleaning using compressed air
at a minimum of: - Correct Answer: 90 psi
11.Special Inspection: - Correct Answer: inspection of construction
requiring unique expertise
12.Proof loading: - Correct Answer: Application of torque to an installed
anchor to verify set, shown as a % of tension capacity
, 13.Proof loads need to meet either: - Correct Answer: 50% of mean bond
strength or 80% of rod yield which ever is smaller
14.In variables N is: - Correct Answer: Tension
15.In variables V is: - Correct Answer: Shear
16.In variables τ is: - Correct Answer: Stress
17.ACI 355.4 applies to anchors with: - Correct Answer: Diameters of 1/4 or
larger with holes drilled to be less than or equal to 1.5d, and an
embedment depth greater than 4d or 1 5/8 and less than 20d
18.minimum anchor spacing and edge distance, as well as minimum member
thickness, must comply with the values given - Correct Answer: In the
products ICC-ES Report
19.The registered design professional in responsible charge and the engineers
of record involved in the design of the project are permitted to act as the -
Correct Answer: Approved Agency
20.If reinforcing bars are encountered during drilling the correct action would
be - Correct Answer: Consulting with the EOR