Question:
The required outlet for an in-ground pool shall be mounted _____
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
a. On the wall of a building 21 feet from waters edge
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
b. On a balcony 8 feet above water level
i,- i,- i,- i,- i,- i,- i,- i,-
c. On a support 3 feet from waters edge
i,- i,- i,- i,- i,- i,- i,- i,-
d. On a post 6'6" above grade level?
i,- i,- i,- i,- i,- i,- i,-
Answer:
d. On a post 6'6" above grade level (See 680.22(A)(1).)
i,- i,- i,- i,- i,- i,- i,- i,- i,-
Question:
Permanently installed pool motors shall have a cord length of_____
i,- i,- i,- i,- i,- i,- i,- i,- i,-
a. 3ft
i,-
b. 6ft
i,-
c. 12ft
i,-
d. 20ft?
i,-
Answer:
,a. 3ft (See 680.21 (A)(3).)
i,- i,- i,- i,-
Question:
The conductor feeding a wet-niche pool light will be _____
i,- i,- i,- i,- i,- i,- i,- i,- i,-
a. Electrical Metallic Conduit
i,- i,- i,-
b. Rigid conduit made of brass
i,- i,- i,- i,- i,-
c. Flexible metallic conduit
i,- i,- i,-
d. Something else.....?
i,- i,-
Answer:
b. Rigid conduit made of brass (See 680.23(B)(2) and (B)(2)(a).)
i,- i,- i,- i,- i,- i,- i,- i,- i,-
Question:
Which conductor is not allowed to be used as a service conductor?
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
a. USE
i,-
b. MC Cable
i,- i,-
c. Underground Feeder
i,- i,-
d. MI Cable?
i,- i,-
Answer:
c. Underground Feeder (See 338.12 (B)
i,- i,- i,- i,- i,-
,Question:
What is the % conduit fill used in a nipple that does not exceed 24"?
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
Answer:
A: 60% (see chapter 9 table 1 note (4).)
i,- i,- i,- i,- i,- i,- i,- i,-
Question:
Car Wash Receptacle must be?
i,- i,- i,- i,-
Answer:
WR Weather Resistant (see 406.9 (B)(1).)
i,- i,- i,- i,- i,-
Question:
Overhead Service conductor clearance for pedestrian walkway?
i,- i,- i,- i,- i,- i,-
Answer:
10' (see 230.24 (B)(1).)
i,- i,- i,-
Question:
Snap switch used for motor must not exceed?
i,- i,- i,- i,- i,- i,- i,-
Answer:
80% of the amp rating of the switch (see 404.14 (A)(3).)
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
, Question:
Max amperage of Edison based fuse?
i,- i,- i,- i,- i,-
Answer:
30A (see 240.51 (A).)
i,- i,- i,-
Question:
What can you put on a small appliance circuit.?
i,- i,- i,- i,- i,- i,- i,- i,-
Answer:
Receptacles for a gas fired range, oven, or countertop cooking unit (see
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
210.52 (B)(2) Exception 2)
i,- i,- i,-
Question:
Type of branch circuit needed for a furnace or other central heating
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
equipment?
Answer:
Individual Branch Circuit (see 422.12) i,- i,- i,- i,-
Question:
A fixed light will be allowed to be 30 amp provided the socket is rated
i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,- i,-
____ duty.
i,-
a. Light
i,-