Fire Alarm Level II Actual Exam Preparation Newest 2025/2026
Complete 200 Questions And Correct Answers (Verified
Answers)|Already Graded A+
Which of the following descriptions would NOT be considered a qualified system
designer?
A. A person who is certified by a state authority.
B. A person who is certified by an internationally recognized certification
organization.
C. A person who is factory trained and certified for fire alarm system design.
D. A person or organization who is approved by the AHJ to design fire alarm
systems. - CORRECT ANSWER=B
If you try to drive a grounding rod and you hit solid rock, you are permitted to bury
the grounding rod in a trench that is at LEAST____deep. - CORRECT
ANSWER=30"
When a raceway is run from the interior to the exterior of a building, the raceway
shall_______.
A. be rigid metal conduit (RMC)
B. be rigid polyvinyl chloride conduit (PVC)
C. be sealed with an approved material
D. have an explosion-proof seal - CORRECT ANSWER=C
When installing smoke detectors in rooms with HVAC diffusers, how far are the
detectors required to be away from the venting? - CORRECT ANSWER=3 feet
,2|Page
Unless otherwise identified, conductors of sizes 14 AWG through 1AWG shall be
rated at_______ - CORRECT ANSWER=60 degrees C
When installing electrical metallic tubing (EMT), the run of tubing is required to
be securely fastened at LEAST every_______(Disregard exceptions) - CORRECT
ANSWER=10 feet
A coded supervisory signal shall be permitted to consist of ___________ rounds of
the number transmitted to indicate a supervisory off-normal condition. -
CORRECT ANSWER=2
Smoke detectors shall not be installed if the temperature is above _____________
degrees F - CORRECT ANSWER=100
A fire alarm system was installed in a protected premises. The FAS is connected to
a supervising station and consists of waterflow detection. Which other device shall
be installed on the protected premises? - CORRECT ANSWER=Manual pull
station
In a protected premises, any trouble signals and its return to normal shall be
displayed within __________ at the FACP. - CORRECT ANSWER=200 seconds
When is a manual fire alarm system NOT required in Group E occupancies?
A. When an automatic sprinkler system is already installed
B. When an automatic fire alarm system is already installed
C. When the occupant load is 50 or less
,3|Page
D. All of the above - CORRECT ANSWER=C
An R-2 apartment building with 20 dwelling units which of the following is true
according to the IBC?
A. a manual fire alarm system that activates the occupant notification is required
B. An automatic fire alarm system with no occupant notification is required
C. Only smoke alarms in each apartment is required for this apartment building
D. No fire alarm system is required for this building - CORRECT ANSWER=A
Two resistors are connected in SERIES; R1 = 40 Ohms, R2 = 10 Ohms, what is the
Resistance of the circuit? - CORRECT ANSWER=50 Ohms
Which of the following circuit pathway designations has a fail-safe operation and
no fault is annunciated? - CORRECT ANSWER=Class D
True/False: Class X is redundant? - CORRECT ANSWER=True
After a loss of primary power, textual visible appliances shall have sufficient
secondary power to operate for a minimum of _____________ of continuous
display time during an emergency event. - CORRECT ANSWER=2 hours
Combination manual fire alarm boxes and __________ shall be permitted?
A. horn/strobes
B. smoke detectors
C. guard's signaling stations
D. none of the above - CORRECT ANSWER=C
, 4|Page
For Groups A-1, A-3, A-4 an automatic sprinkler system is required if fire area is
greater than _______________ sq ft - CORRECT ANSWER=12,000 sq ft
For Group A-2 an automatic sprinkler system is required if fire area is greater than
____________________ sq ft - CORRECT ANSWER=5,000 sq ft
For Groups A-1, A-2, A-3 an automatic sprinkler system is required if occupancy is
greater than _____________ people - CORRECT ANSWER=300
For Groups S-1, sprinklers are required in areas greater than __________ sq ft -
CORRECT ANSWER=12,000 sq ft
For Groups S-1 that houses commercial motor vehicles sprinklers are required in
areas greater than ________________ sq ft - CORRECT ANSWER=5,000 sq ft
The International Mechanical Code requires a duct smoke detector in the return for
units over ________ cfm - CORRECT ANSWER=2000 cfm
The International Mechanical Code (IMC) requires a duct smoke detector in the
supply for units over __________ cfm - CORRECT ANSWER=15000
Digital alarm communicator transmitters (DACT) which use call forwarding to the
DACR shall be tested with what frequency? - CORRECT ANSWER=4 hours
NPLFA cables shall be insulated to __________ v - CORRECT ANSWER=600v