NYC Master Electrical Exam
neutral point - correct anwersThe common point on a wye-connection in a polyphase system or
midpoint on a single phase, 3-wire system, or midpoint of a single phase portion of a 3-phase
delta system, or a midpoint of a 3-wire, direct current system
In the NEC the words ___________indicate a mandatory requirement - correct anwersShall or
shall not
On a four wire Delta connected system with a midpoint of one phase winding is grounded, only
the conductor or bus bar having a higher phase voltage the ground shall be durably and
permanently marked by an outer finish that is _______ in color or by other effective means.
Such Identification shall be placed at each point on the system where connection is made if the
grounded conductor is also present. - correct anwersOrange
The required working space for access to live parts operating at 300 V to ground, where there
are exposed live parts on one side and grounded parts on the other side is ____________. -
correct anwers3 feet 6 inches
The dimensions of working space for access to live parts operating at 300 V, nominal to ground,
where there are expose live parts on both sides of the workspace is________________. -
correct anwers4 feet
110.26 A1- Dead front assemblies working space - correct anwers30" for non-electrical parts
36" for electrical parts
The working space in front of the electrical equipment shall not be less than _______wide, or of
the width of the equipment, whichever is greater. - correct anwers30"
Large equipment - correct anwers1200 A or greater and over 6 feet wide
Large equipment means of egress - correct anwersTwo means of egress 24" wide by 6.5 feet tall
unless the following condutions are met
1) unobstructed egress
2) Double the workspace
,Headroom shall not be less than _______. - correct anwers6.5 feet or the height of the
equipment
Live parts of electrical equipment operating at ______volts or more she'll be guarded against
accidental contact or approved enclosures or by any of the following means - correct anwers50
volts
4) by elevation of 8 feet or more above the floor or other working surface
A fence shall not be less than ______feet in height - correct anwers8 feet
One entrance to enclosures for electrical installations as described in 110.31 not less than
_______wide and _________high shall be provided to give access to the working space around
the electrical equipment - correct anwers30 inches and 6.5 feet
Network compartments shall have at least ________means of access. Each door she'll have an
access that leads to a legal exit. - correct anwersTwo
Where rear access is required to work on deenergized parts on the back of enclosed equipment
a minimum working space of __________horizontally shall be provided - correct anwers30
inches
All non-current carrying metal parts of electrical equipment and all metal raceways and cable
shall be solidly grounded and bonded to all metal pipes in rails at the portal and the intervals
not exceeding _____________throughout the tunnel. - correct anwers1000 feet
Manhole workspace for cabling-A clear workspace not less than _______wide shall be provided
were cables are located on both sides and not less than _______were cables are only on one
side. - correct anwers3 feet
2-1/2 feet
Access to manhole dimensions. Rectangular access openings shall not be less than _______.
Round access openings in a manhole shall be not less than ______inches in diameter - correct
anwers26" x 22"
26"
Manhole openings for personnel shall be located where they are not directly above electrical
equipment or conductors in the enclosure. Where this is not practiceable either a ________or a
_______shall be provided. - correct anwersProtective barrier of fixed ladder
And insulated grounded conductor of _____or smaller shall be identified by a continuous white
or gray outer finish or by three continuous white stripes on other than green insulation along its
entire length. - correct anwers6 awg
,Manhole covers shall be over ______pounds or otherwise designated to require the use of tools
to open. - correct anwers100 pounds
The grounded conductors of other systems shall have a different outer covering conforming to
200.6A or 200.6B or by an outer covering of ______or _______with a readily distinguishable
colored stripe other than green running along the insulation - correct anwersWhite or gray
Where conductors of different systems are installed in the same race way, one system she'll
have a neutral having an outer covering of white or natural gray and each other system having a
neutral shall have an another covering of - correct anwersWhite with colored Stripe other than
green or distinguish by other suitable approved means
For screw shell devices with attach leads the conductor attached to the screw shell shall have a
_______or ________finish. - correct anwersWhite or gray
In addition to the number of branch circuits required by other parts of the section _______or
more 20 A small appliance branch circuits shall be provided for all receptacle outlets specified
by 210.52B. - correct anwersTwo
An individual branch circuit shall be provided for each _________receptacle required by 210.52
I. - correct anwersAir-Conditioning
Branch circuits required in a dwelling unit. - correct anwers1) small appliance branch circuit
2) laundry branch circuit
3) bathroom branch circuits
4) Air-Conditioning (NYC AMEND)
The maximum voltage drop on branch circuit conductors is _________percent. - correct
anwers3%
Overall 5%
The maximum voltage drop on feeder circuits is ________. - correct anwers2%
Overall 5%
Dwelling unit circuits running through another dwelling unit in common areas. What percentage
of change will require it to be brought up to current code? - correct anwers50%
Receptacle outlets in floors shall not be counted as part of the required number of receptacle
outlets unless located within _________of the wall. - correct anwers18"
, Outlets may be installed in a dwelling unit for specific appliance such as laundry equipment.
What is the maximum distance allowed between this outlet and the appliance? - correct
anwers6 feet
A receptacle connected to one of the dwelling unit small appliance branch circuits can be used
to supply a(n) __________in any of the rooms specified in 210.52B1. - correct anwersElectric
clock
How many receptacles are required within the perimeter of a balcony, deck or porch with a
usable area of less than 20 ft.² - correct anwers1
The number of receptacle outlets for guest rooms in hotels and motels shall not be less than
required for a dwelling unit. These receptacles can be located to be convenient for permanent
furniture layout but at least _________receptacle outlets shall be readily accessible. - correct
anwers2
At least one receptacle outlet shall be installed within _______of the top of a show window for
each 12 linear feet measured horizontally across its length. - correct anwers18"
A 125 V single phase 15 or 20 amp rated receptacle outlet shall be installed at an accessible
location for the servicing of heating air-conditioning and refrigeration equipment the receptacle
shall be located on the same level and within _______of the heating air-conditioning and
refrigeration equipment the receptacle outlet shall not be connected to the load side of the
equipment disconnecting means. - correct anwers25 feet
Permanently installed electric baseboard heaters equipped with factory install receptacle
outlets or outlets provided as a separate assembly by the manufacturer shall be permitted as
the required outlet or outlets for the wall space utilized by such permanently installed heaters
such receptacle outlets __________be connected to the heater circuits. - correct anwersShall
not
Where a range, counter mounted cooking unit or sink is installed in an island or peninsula
countertop and the width of the countertop behind the range, counter mounted cooking unit or
sink is less than ________the range, counter mounted cooking unit or sink is considered divide
the countertop space into two separate countertop spaces. - correct anwers12"
Receptacle outlets shall be located above but not more than ________ above the countertop. -
correct anwers20 inches
In dwelling units at least one receptacle outlet shall be installed in bathrooms within
__________of the outside edge of each basin or installed on the side or face of the basin
cabinet not more than ______below the countertop. - correct anwers3 feet
neutral point - correct anwersThe common point on a wye-connection in a polyphase system or
midpoint on a single phase, 3-wire system, or midpoint of a single phase portion of a 3-phase
delta system, or a midpoint of a 3-wire, direct current system
In the NEC the words ___________indicate a mandatory requirement - correct anwersShall or
shall not
On a four wire Delta connected system with a midpoint of one phase winding is grounded, only
the conductor or bus bar having a higher phase voltage the ground shall be durably and
permanently marked by an outer finish that is _______ in color or by other effective means.
Such Identification shall be placed at each point on the system where connection is made if the
grounded conductor is also present. - correct anwersOrange
The required working space for access to live parts operating at 300 V to ground, where there
are exposed live parts on one side and grounded parts on the other side is ____________. -
correct anwers3 feet 6 inches
The dimensions of working space for access to live parts operating at 300 V, nominal to ground,
where there are expose live parts on both sides of the workspace is________________. -
correct anwers4 feet
110.26 A1- Dead front assemblies working space - correct anwers30" for non-electrical parts
36" for electrical parts
The working space in front of the electrical equipment shall not be less than _______wide, or of
the width of the equipment, whichever is greater. - correct anwers30"
Large equipment - correct anwers1200 A or greater and over 6 feet wide
Large equipment means of egress - correct anwersTwo means of egress 24" wide by 6.5 feet tall
unless the following condutions are met
1) unobstructed egress
2) Double the workspace
,Headroom shall not be less than _______. - correct anwers6.5 feet or the height of the
equipment
Live parts of electrical equipment operating at ______volts or more she'll be guarded against
accidental contact or approved enclosures or by any of the following means - correct anwers50
volts
4) by elevation of 8 feet or more above the floor or other working surface
A fence shall not be less than ______feet in height - correct anwers8 feet
One entrance to enclosures for electrical installations as described in 110.31 not less than
_______wide and _________high shall be provided to give access to the working space around
the electrical equipment - correct anwers30 inches and 6.5 feet
Network compartments shall have at least ________means of access. Each door she'll have an
access that leads to a legal exit. - correct anwersTwo
Where rear access is required to work on deenergized parts on the back of enclosed equipment
a minimum working space of __________horizontally shall be provided - correct anwers30
inches
All non-current carrying metal parts of electrical equipment and all metal raceways and cable
shall be solidly grounded and bonded to all metal pipes in rails at the portal and the intervals
not exceeding _____________throughout the tunnel. - correct anwers1000 feet
Manhole workspace for cabling-A clear workspace not less than _______wide shall be provided
were cables are located on both sides and not less than _______were cables are only on one
side. - correct anwers3 feet
2-1/2 feet
Access to manhole dimensions. Rectangular access openings shall not be less than _______.
Round access openings in a manhole shall be not less than ______inches in diameter - correct
anwers26" x 22"
26"
Manhole openings for personnel shall be located where they are not directly above electrical
equipment or conductors in the enclosure. Where this is not practiceable either a ________or a
_______shall be provided. - correct anwersProtective barrier of fixed ladder
And insulated grounded conductor of _____or smaller shall be identified by a continuous white
or gray outer finish or by three continuous white stripes on other than green insulation along its
entire length. - correct anwers6 awg
,Manhole covers shall be over ______pounds or otherwise designated to require the use of tools
to open. - correct anwers100 pounds
The grounded conductors of other systems shall have a different outer covering conforming to
200.6A or 200.6B or by an outer covering of ______or _______with a readily distinguishable
colored stripe other than green running along the insulation - correct anwersWhite or gray
Where conductors of different systems are installed in the same race way, one system she'll
have a neutral having an outer covering of white or natural gray and each other system having a
neutral shall have an another covering of - correct anwersWhite with colored Stripe other than
green or distinguish by other suitable approved means
For screw shell devices with attach leads the conductor attached to the screw shell shall have a
_______or ________finish. - correct anwersWhite or gray
In addition to the number of branch circuits required by other parts of the section _______or
more 20 A small appliance branch circuits shall be provided for all receptacle outlets specified
by 210.52B. - correct anwersTwo
An individual branch circuit shall be provided for each _________receptacle required by 210.52
I. - correct anwersAir-Conditioning
Branch circuits required in a dwelling unit. - correct anwers1) small appliance branch circuit
2) laundry branch circuit
3) bathroom branch circuits
4) Air-Conditioning (NYC AMEND)
The maximum voltage drop on branch circuit conductors is _________percent. - correct
anwers3%
Overall 5%
The maximum voltage drop on feeder circuits is ________. - correct anwers2%
Overall 5%
Dwelling unit circuits running through another dwelling unit in common areas. What percentage
of change will require it to be brought up to current code? - correct anwers50%
Receptacle outlets in floors shall not be counted as part of the required number of receptacle
outlets unless located within _________of the wall. - correct anwers18"
, Outlets may be installed in a dwelling unit for specific appliance such as laundry equipment.
What is the maximum distance allowed between this outlet and the appliance? - correct
anwers6 feet
A receptacle connected to one of the dwelling unit small appliance branch circuits can be used
to supply a(n) __________in any of the rooms specified in 210.52B1. - correct anwersElectric
clock
How many receptacles are required within the perimeter of a balcony, deck or porch with a
usable area of less than 20 ft.² - correct anwers1
The number of receptacle outlets for guest rooms in hotels and motels shall not be less than
required for a dwelling unit. These receptacles can be located to be convenient for permanent
furniture layout but at least _________receptacle outlets shall be readily accessible. - correct
anwers2
At least one receptacle outlet shall be installed within _______of the top of a show window for
each 12 linear feet measured horizontally across its length. - correct anwers18"
A 125 V single phase 15 or 20 amp rated receptacle outlet shall be installed at an accessible
location for the servicing of heating air-conditioning and refrigeration equipment the receptacle
shall be located on the same level and within _______of the heating air-conditioning and
refrigeration equipment the receptacle outlet shall not be connected to the load side of the
equipment disconnecting means. - correct anwers25 feet
Permanently installed electric baseboard heaters equipped with factory install receptacle
outlets or outlets provided as a separate assembly by the manufacturer shall be permitted as
the required outlet or outlets for the wall space utilized by such permanently installed heaters
such receptacle outlets __________be connected to the heater circuits. - correct anwersShall
not
Where a range, counter mounted cooking unit or sink is installed in an island or peninsula
countertop and the width of the countertop behind the range, counter mounted cooking unit or
sink is less than ________the range, counter mounted cooking unit or sink is considered divide
the countertop space into two separate countertop spaces. - correct anwers12"
Receptacle outlets shall be located above but not more than ________ above the countertop. -
correct anwers20 inches
In dwelling units at least one receptacle outlet shall be installed in bathrooms within
__________of the outside edge of each basin or installed on the side or face of the basin
cabinet not more than ______below the countertop. - correct anwers3 feet